This user manual describes the features and specifications of the Contemporary Controls BAST-221C/CH-B2 BACnet Communicating Thermostat.
The BAST-221C/CH-B2 is a member of the Contemporary Controls BASstat series of BACnet communicating thermostats. It provides multi-stage heating and cooling control for rooftop units in a wall-mounted enclosure with a large LCD display, and uses BACnet MS/TP over 2-wire EIA-485.
The manual covers features and benefits, specifications, installation and wiring, user mode and control type operation, the Engineering Mode menu, and BACnet object and network configuration. The 221CH models also support relative humidity reading with a built-in sensor and a calculated dew point value as a BACnet object.
| Supply Voltage and Current | 24 VAC (±10%), 5 VA |
|---|---|
| Relay Contact Rating | SPST 2A at 30 VAC with inductive load |
| Protocol Compliance | BACnet MS/TP with B-ASC, BTL Listed |
| Baud Rate | 9.6, 19.2, 38.4, 76.8 kbps (default 38.4 kbps) |
| Temperature Display Range | 14 to 140°F (-10 to +60°C) |
| Setpoint Range | 32 to 122°F (0 to 50°C) |
| Relative Humidity | 5 to 95% non-condensing |
| Dimensions | Width 94 mm, height 118 mm, depth 34 mm |
| Remote Temperature Sensor | NTC Type 3kΩ thermistor |
It uses BACnet MS/TP with a B-ASC device profile and is BTL listed.
It has five relays: two for stage heating, two for stage cooling and one for the fan.
It requires 24 VAC (±10%) at 5 VA.
Yes, the thermostat has provision for an NTC Type 3kΩ thermistor remote sensor.