Clark Cooper EH Series Solenoid Valve Installation, Operation and Maintenance Manual

The document provides the installation, operation and maintenance manual for EH series solenoid valves.


Clark Cooper EH Series Solenoid Valve Installation, Operation and Maintenance Manual - cover page
Brand
Clark Cooper
Category
Industrial Supply
Document type
Service Manual
Language
Chinese
Pages
8
File format
PDF
File size
2.6 MB
Published
08 November, 2023
Updated
08 November, 2023
MD5 checksum
9FA7ACEE1B3D42CB36A353686A4B5717

About this manual

This technical manual, identified as EH-1.2, covers the installation, operation and maintenance of Clark Cooper EH series solenoid valves, with separate instructions for the EH30, EH40, EH50 and EH70 models. It explains valve sizing terms such as full port and reduced port, the flow coefficient Cv, and the equation used to calculate flow, Cv or pressure drop.

The installation sections cover valve orientation, threaded, welded, flanged and compression end connections, electrical wiring and conduit requirements, and a wiring diagram. The manual also describes the difference between pilot-operated and direct-acting valves, warns about debris and hot solenoids, and gives step-by-step procedures for replacing the solenoid and the piston assembly on EH30, EH40/EH50 and EH70 valves. This manual is written in Chinese.

What's inside

  • Valve sizing and Cv
  • Installation
  • Valve orientation
  • Port connections
  • Electrical connection
  • Pilot-operated and direct-acting valves
  • Maintenance and repair
  • Solenoid replacement
  • Piston assembly replacement

Specifications

Conduit connection1/2" FNPT on the standard solenoid enclosure
Lead lengthAt least 18 in.; custom lengths and wire types available
Minimum wire gauge18 AWG
Voltage tolerance±10% of rated voltage unless otherwise stated
Maximum cycling rate4 cycles per minute unless designed for a high cycle rate
Minimum operating pressure, EH40 and EH50 pilot-operated valves50 PSI for EH40, 100 PSI for EH50
Weld temperature limit400 °F

Frequently asked questions

What do full port and reduced port mean for these solenoid valves?

A full port valve has a connection size equal to the valve orifice, while a reduced port valve has a pipe connection larger than the orifice; a full port valve has the higher Cv.

How should EH30, EH40 and EH50 valves be oriented?

The inlet is horizontal, the outlet faces down and the solenoid coil sits on top. EH70 valves can be mounted in any orientation.

What is the minimum inlet pressure for EH40 and EH50 pilot-operated valves?

EH40 valves require 50 PSI and EH50 valves require 100 PSI, up to the rated pressure.

Can the solenoid be rotated to position the conduit connection?

Yes. Loosen the nut on top of the solenoid coil, rotate the solenoid up to 360°, then retighten the nut.

Download PDF (2.6 MB)