The document provides the installation, operation and maintenance manual for EH series solenoid valves.
This technical manual, identified as EH-1.2, covers the installation, operation and maintenance of Clark Cooper EH series solenoid valves, with separate instructions for the EH30, EH40, EH50 and EH70 models. It explains valve sizing terms such as full port and reduced port, the flow coefficient Cv, and the equation used to calculate flow, Cv or pressure drop.
The installation sections cover valve orientation, threaded, welded, flanged and compression end connections, electrical wiring and conduit requirements, and a wiring diagram. The manual also describes the difference between pilot-operated and direct-acting valves, warns about debris and hot solenoids, and gives step-by-step procedures for replacing the solenoid and the piston assembly on EH30, EH40/EH50 and EH70 valves. This manual is written in Chinese.
| Conduit connection | 1/2" FNPT on the standard solenoid enclosure |
|---|---|
| Lead length | At least 18 in.; custom lengths and wire types available |
| Minimum wire gauge | 18 AWG |
| Voltage tolerance | ±10% of rated voltage unless otherwise stated |
| Maximum cycling rate | 4 cycles per minute unless designed for a high cycle rate |
| Minimum operating pressure, EH40 and EH50 pilot-operated valves | 50 PSI for EH40, 100 PSI for EH50 |
| Weld temperature limit | 400 °F |
A full port valve has a connection size equal to the valve orifice, while a reduced port valve has a pipe connection larger than the orifice; a full port valve has the higher Cv.
The inlet is horizontal, the outlet faces down and the solenoid coil sits on top. EH70 valves can be mounted in any orientation.
EH40 valves require 50 PSI and EH50 valves require 100 PSI, up to the rated pressure.
Yes. Loosen the nut on top of the solenoid coil, rotate the solenoid up to 360°, then retighten the nut.