CHUNDE CMP-XX15 Auto-Tune Fuzzy/PID Process/Temperature Controller Communication Manual

CHUNDE Auto-Tune Fuzzy / PID Process / Temperature Controller CMP-XX15 is a multi-function temperature controller with the following features: 1. Supports a variety of input sensors, including thermocouples and thermal resistors. 2. Has an automatic adjustment function, which can automatically adjust PID parameters according to the characteristics of the controlled object. 3. Has a fuzzy control function, which can perform fuzzy control according to the characteristics of the controlled object. 4. Has a PID control function, which can perform PID control according to the characteristics of the controlled object. 5. Has a variety of output methods, including relay output, analog output and digital output. 6. Has a variety of alarm methods, including upper limit alarm, lower limit alarm and deviation alarm. 7. Has a variety of communication methods, including RS-485 communication and Modbus communication. 8. Has a variety of protection functions, including over-temperature protection, over-current protection and short-circuit protection.


CHUNDE CMP-XX15 Auto-Tune Fuzzy/PID Process/Temperature Controller Communication Manual - cover page
Brand
CHUNDE
Category
Other products
Document type
Programming Manual
Language
English
Pages
29
File format
PDF
File size
745 KB
Published
08 November, 2023
Updated
08 November, 2023
MD5 checksum
F082DB9BA4E4920B780F8CA30D9E3332

About this manual

This document is the communication manual for the CHUNDE CMP-XX15 Auto-Tune Fuzzy/PID process/temperature controller. It lists Modbus register parameters with their descriptions, ranges, default values, and data access types.

It also includes parameter mapping information and an error code table with descriptions, reasons, and corrective actions.

What's inside

  • Parameters Description
  • Modbus Register Address
  • Parameter Mapping
  • Error Code
  • Corrective Action

Specifications

Default set point 125.0°C (77.0°F)
Input unit selection°C, °F, or process unit
Decimal point selection0 to 3 decimal digits
Filter damping time constant0 to 60 seconds
Proportional band0.0 to 500.0°C (900.0°F)
Integral time0 to 3600 sec
Derivative time0.0 to 360.0 sec
Output 1 cycle time0.1 to 90.0 sec

Frequently asked questions

What is the default value of set point 1?

The default value of set point 1 is 25.0°C (77.0°F).

What does error code ER04 indicate?

ER04 indicates illegal setup values used for cooling output configuration.

How should communication error ER10 be corrected?

Correct the communication software to meet the protocol requirements.