NPM502 networked power meter is a universal data acquisition module specially developed for water supply automatic control, urban water treatment automatic control, heat network pipeline automatic control, oil field gathering and transferring oil station, hot water boiler, industrial steam boiler monitoring, water source well, and pumping station remote control.
The NPM502 networked power meter from Tengkong is a general data acquisition module for automated control applications such as water supply, water treatment, heating networks, oil transfer stations, boilers, water source wells, and pump stations. It can be used as a standalone module for on-site parameter indication or expanded through an RS485 communication port; when more than 32 meters are used, an SCM communication management module concentrates data to the host computer.
The manual describes the meter's three-phase AC measurement functions, panel layout and operation, MODBUS communication protocol and data definitions, installation and wiring, typical system configuration, and ordering requirements. This manual is written in Chinese.
| Measurement method | Three-meter method, angular or star connection |
|---|---|
| Measured lines | One line |
| Measured object | Three-phase phase or line voltage and three-phase current |
| Input voltage | 0-400 V (0-100 V customizable) |
| Input voltage overload | Long-term 50% overload |
| Input voltage linear range | 150% |
| Input current | 0-5 A |
| Input current long-term overload | 120% |
| Input current instantaneous overcurrent | 2 times |
| Input current linear range | 200% |
| Sampling rate | 32 points per cycle |
| Data refresh speed | 40 ms |
| AC measurement frequency range | 20-65 Hz |
| Frequency measurement accuracy | ±0.01 Hz ±1 digit |
| Measurement accuracy | 0.5% FS ±2 digits |
| Three-phase voltage display range | Not greater than 24000 V |
| Three-phase current display range | Not greater than 12000 A |
| Three-phase active power display range | Absolute value not greater than 300000 kW |
| Three-phase reactive power display range | Absolute value not greater than 300000 kVar |
| Total active power display range | Absolute value not greater than 900000 kW |
| Total reactive power display range | Absolute value not greater than 900000 kVar |
| Energy display range | Not greater than 5000000000 kWh |
| Power factor display | Actual value |
| Frequency display | Actual frequency, 0.01 Hz, 35-65 Hz |
| Communication interface | RS485 and RS232 optional |
| Communication protocol | MODBUS |
| Installation method | Standard panel mounting |
| Operating temperature | -25 to 55 C |
| Storage temperature | -40 to 70 C |
| Relative humidity | Less than 85% (at 20±5 C) |
| Atmospheric pressure | 86-108 kPa |
| Installation dimensions | 96 x 96 x 110 mm |
| Panel cutout | 92 x 92 mm |
| Power supply | AC 85-265 V 50/60 Hz or DC 24 V ±30% |
| Power consumption | Less than 5 W |
| Harmonics | 1-15th harmonics |
It supports the MODBUS protocol.
AC 85-265 V at 50/60 Hz or DC 24 V ±30%.
The installation dimensions are 96 x 96 x 110 mm.
Yes, it can measure inverter output.