The emergency lighting controller adopts a self-developed control motherboard, which can accurately and reliably communicate with the emergency power supply and lamps.
The Taiyi TY-C-10W01B2 is an emergency lighting controller that acts as the control core of a centralized-power, centrally-controlled fire emergency lighting and evacuation indication system, working together with the company's emergency power supplies and fire emergency luminaires. It has a 10.0-inch LCD screen with touch control, two CAN bus loops for communication with emergency power supplies, monitoring of up to 3200 individually addressed fire emergency luminaires, and multiple serial ports for linkage with other fire control equipment. The document states that the controller follows the GB17945-2010 national standard.
The manual covers the product overview and intended use, technical characteristics and main parameters, structural features and wiring, installation and commissioning including cabling requirements, operating functions such as login, settings, registration, emergency plans, fault and history queries, monthly/annual inspection, emergency/stop/reset/mute/self-test and linkage modes, plus troubleshooting, safety devices, maintenance, packaging and storage, unpacking checks and after-sales service. The unit measures 482 mm × 267 mm × 76 mm, weighs 6.5 kg gross and is built for flush mounting, with optional wall cabinet, floor cabinet or console installation. This manual is written in Chinese.
| Rated supply voltage | AC220V, 50Hz |
|---|---|
| Backup battery | DC3.2V, 6Ah |
| Display | 10.0-inch LCD screen |
| Bus type | CAN-BUS |
| Transmission distance | ≤1000 m (wiring cross-section not less than 1.5 mm²) |
| Number of loops | 2 loops, expandable |
| Communication interfaces | CAN, RS485, USB |
| Monitored addressable luminaires | Up to 3200 |
| Dimensions | 482 mm × 267 mm × 76 mm |
| Gross weight | 6.5 kg |
| Operating ambient temperature | 0 to +55 °C |
| Relative humidity | ≤85% |
| Linkage interfaces | 8 interfaces, DC24V active or passive linkage |
It is rated for AC220V at 50 Hz, with a DC3.2V 6Ah backup battery.
It can monitor 3200 fire emergency luminaires with independent addresses.
The manual lists "no main power" as the cause and advises checking the main power connection line.
The repeat power-on interval should be longer than 5 seconds.