SERVOSAN ® KURTARAN® KGS-series BATTERY POWERED EMERGENCY EVACUATION DEVICE USER’S MANUAL
The Servosan Kurtaran KGS-series is a battery-powered emergency evacuation device for elevators. According to the manual, it starts automatically when mains power fails and moves the cabin to the upper or lower floor to rescue people inside. The manual covers the INT9-V2 control unit, the SR battery charger, main controller connection, battery selection and connection, operation, program bridges, display indications, fault diagnosis and periodic maintenance.
The manual lists use for elevator motors up to 16 HP and battery arrangements using four 12 V 7 Ah batteries up to 8.2 HP or four 12 V 12 Ah batteries for 8.2–16 HP motors. It also gives a safety warning to turn off the W-automat and disconnect the 48+ battery terminal before maintenance.
| Maximum elevator motor power | 16 HP |
|---|---|
| Battery configuration up to 8.2 HP | Four 12 V 7 Ah batteries in series (48 V 7 Ah) |
| Battery configuration for 8.2–16 HP | Four 12 V 12 Ah batteries |
| Maximum battery cable length | 150 cm |
| Minimum battery cable cross-section | 6 mm² (10 mm² for 8.2–16 HP motors) |
| Battery charger output voltage | Up to 55.2 V when fully charged |
| Cabin lamp | 12 V, 3 W |
The KGS starts automatically and moves the elevator cabin to the upper or lower floor to rescue people inside.
Turn off the W-automat on the KGS unit and disconnect the cable on the 48+ terminal on the battery.
It remains on for two more minutes.
Four 12 V 12 Ah batteries must be used instead of 7 Ah batteries.