The document describes the operating instructions of the Statox 503 control module.
The Statox 503 Control Module from Compur Monitors is a DIN-rail module for gas detection systems. It can operate as a Control Module that supplies sensor heads for toxic or combustible gases and converts their signals into a 4–20 mA analog output, or as a Common Alarm Module that collects alarm signals from up to 25 connected control modules.
This manual covers mounting and dismounting on DIN rail TS 35, 24 VDC power connection, start-up, controls and LEDs, communication bus and electrical connections, password and menu structure, Service Mode, calibration, alarm relay programming, functional test, status and error messages, and safety functions.
| Operating modes | Control Module or Common Alarm Module |
|---|---|
| Power supply | 24 VDC |
| Mounting | DIN rail TS 35 |
| Analog output | 4–20 mA |
| Common Alarm capacity | Up to 25 connected control modules |
| Power rail capacity | 30 modules max. in one row |
| Terminal capacity | Max. 2.5 mm² |
| Controls | Four push buttons |
| Status LEDs | 4 status LEDs |
It can operate as a Control Module, supplying sensor heads and handling their signals, or as a Common Alarm Module that collects alarm signals from up to 25 connected control modules.
The module is inclined and moved to the lower part of the DIN rail, then pushed forward against the spring lock until it snaps in.
The red S LED indicates a failure or service request; it flashes in Service Mode, is on for System Failure, and is off in Measuring mode.
An error message (ERROR 2 or ERROR 5, depending on the measuring program) is generated; activate the appropriate program first, then connect the sensor head.