The BEKA power isolator is an intrinsically safe device that is used to power intrinsically safe equipment. It can be installed in hazardous areas and has multiple certifications.
This Application Guide describes the function of BEKA Power Isolators and how they may safely be used. They are primarily intended for powering BEKA intrinsically safe Pageant Operator Panels, but may also be used to power any intrinsically safe apparatus having compatible input safety parameters.
The BA212 single channel and BA243 four channel Power Isolators are powered by a 24V dc supply, certified as associated apparatus with Ex ia IIC certification, and clip onto a standard 35mm DIN rail for installation in a safe area or Zone 2, 21 or 22 with additional mechanical protection.
| Output voltage Uo | 12.4V |
|---|---|
| Output current Io | 2.66A |
| Output power Po | 5.2W |
| Max external capacitance Co | 1.24µF / 7.9µF / 30.0µF |
| Max external inductance Lo | 5µH / 20µH / 40µH |
| Supply voltage | 24V dc |
| Maximum supply Um | 30V |
They have a Um of 30V and must be powered from a 30V maximum dc supply.
They are usually installed in a safe area, but with additional mechanical protection may be installed in Zone 2, 21 or 22.
Both have IECEx, ATEX and UKEX associated apparatus intrinsic safety Ex ia IIC certification.
Yes, all BEKA Power Isolators have ia level protection and may be used to power apparatus located in Zone 0.