Kidde-Fenwal WHDR-125 WHDR-260 Marine Fire Extinguishing System Certificate

This product is a marine fire extinguishing equipment, featuring fast extinguishing speed and high efficiency.


Kidde-Fenwal WHDR-125 WHDR-260 Marine Fire Extinguishing System Certificate - cover page
Brand
Kidde-Fenwal
Category
Other
Document type
Other
Language
English
Pages
3
File format
PDF
File size
209 KB
Published
06 November, 2023
Updated
06 November, 2023
MD5 checksum
CB2BAAAFC2072A5CA9D20C68740311CC

About this manual

This is a DNV GL MED certificate issued under the authority of the Government of the Kingdom of Norway for Kidde-Fenwal WHDR-125 and WHDR-260 Wet Chemical Systems. The certified product is a deep-fat cooking equipment fire extinguishing system, automatic or manual type, consisting of spray nozzles, piping, section valves as applicable, cylinders and a mechanical release module; it is a pressure vessel system. The certificate states compliance with Council Directive 96/98/EC as amended by 2014/93/EU, SOLAS 74 regulations II-2/1, II-2/10 and X/3, and the 2000 HSC Code 7.

The document describes the system components and specifications, including Kidde APC Wet Agent, Type “F” nozzles, 15 mm steel pipes, nitrogen expellant gas, and cylinder capacities of 5 L for WHDR-125 and 10 L for WHDR-260. It also lists installation testing requirements, including pressure testing of the pipe system to at least 1.5 times maximum working pressure and function testing, and periodical testing according to the maker's manual. The certificate addresses only SOLAS Ch. II-2, Reg. 10, 6.4.1; compliance with the shutdown function in 6.4.2–6.4.5 must be verified in each case.

What's inside

  • Product description
  • Application/Limitation
  • System components
  • System specifications
  • Installation testing
  • Periodical testing
  • Type Examination documentation
  • Tests carried out
  • Marking of product

Specifications

System typeWHDR-125 and WHDR-260 Wet Chemical System
Extinguishing agentKidde APC Wet Agent
Piping system15 mm steel pipes
Expellant gasNitrogen
Cylinder capacity, WHDR-1255 L
Cylinder capacity, WHDR-26010 L
Vertical distance from vat762 to 1270 mm
Maximum vat/protected area495 x 641 mm
Cylinder operating pressureMax. 13 bar

Frequently asked questions

What equipment is the WHDR-125/WHDR-260 system approved to protect?

It is approved for use as a fire extinguishing system for galley deep-fat cooking equipment.

Which model covers two fryers?

The WHDR-260 is listed for 2 fryers.

What is the maximum cylinder operating pressure?

The maximum cylinder operating pressure is 13 bar.

What standard was the system tested to?

The system was tested according to ISO 15371:2009.