HAUBER-Elektronik Type 656 A/B Evaluation Device Instruction Manual

This document is an instruction manual for the evaluation device 656 A/B, which is used for current signal detection and evaluation of vibration controls.


HAUBER-Elektronik Type 656 A/B Evaluation Device Instruction Manual - cover page
Brand
Hauber Elektronik
Category
Industrial Supply
Document type
User Manual
Language
English
Pages
7
File format
PDF
File size
1.3 MB
Published
06 November, 2023
Updated
06 November, 2023
MD5 checksum
EBAC9B11C96011DCC05F7AE8C99EA454

About this manual

The HAUBER-Elektronik Type 656 A and B are evaluation devices designed for the current-signal detection and evaluation of vibration controls. The Type 656 A is intended for industrial applications where specific vibration values must not be exceeded, such as fans, motors, and pumps. The Type 656 B is used for applications where vibration must not be lower than a specific value, such as conveyor and sieving equipment.

What's inside

  • Intended Use
  • Input and Output Signals
  • Switching Threshold and Delay
  • Relay Contacts
  • Device Conditions
  • Alarm Conditions
  • Connections
  • Electrical Data
  • Mechanical Data

Specifications

Input signalCurrent-signal 4...20 mA
Output signalOK-Relay-Contact, Alarm-Relay-Contact
Voltage supply for sensor24 V DC
Switching thresholdbetween 4...20 mA, infinitely adjustable
Delaybetween 0...30 s, infinitely adjustable
Switching voltage max250 V AC
Power consumptionca. 1 VA
Working temperature0°C...+70°C
Weightapp. 200 g
Protection gradeIP 40

Frequently asked questions

What is the intended use of the Type 656 A?

The Type 656 A is applied for the current-signal detection and evaluation of vibration controls in industrial equipment where a specific vibration value must not be exceeded.

What is the intended use of the Type 656 B?

The Type 656 B is applied for the current-signal detection and evaluation of vibration controls in two-wire technology where the vibration must not be lower than a specific value.

What happens if there is a cable break?

In case of a cable break, the OK-LED is BLINKING and the OK-Relay-Contacts 5 and 4 are closing.