This document is the instruction manual of the GD-27BP type bypass pressure reducing valve from Yaoshidakai, which introduces the product's specifications, performance, structure, function, setting, operation, maintenance and other contents.
This user manual covers the Yaoshidakai EPDT-279b and GD-27BP bypass pressure reducing valves for cold and hot water. The valves come in nominal diameters 20A to 100A, handle a primary side pressure up to 1.0 MPa, and operate with fluid temperatures from 5 to 90 °C.
The document describes specifications and performance, dimensions and mass, structure and function, pressure-reducing operation, product setup, operation, maintenance, the exploded view, and after-sales service. It also lists tightening torques and the adjustment and maintenance tools. This manual is written in Chinese.
| Model | GD-27BP |
|---|---|
| Nominal diameter | 20A~100A |
| Applicable fluid | Cold and hot water |
| Primary side pressure | 1.0 MPa or below |
| Secondary side pressure | A: 0.05~0.35 MPa; B: 0.30~0.70 MPa |
| Minimum pressure differential | 0.05 MPa |
| Maximum pressure reduction ratio | 10:1 |
| Fluid temperature | 5~90 °C |
| Connection | JIS 10KFF flange |
One year after delivery to the user and start of test operation, but at most 24 months after shipment from the Yaoshidakai factory.
A 60-mesh filter is recommended.
Install it 3 m or more away from the product.