Tenghui TGRJ Series Medium and High Voltage Motor Solid State Soft Starter User Manual

This manual introduces the TGRJ series medium and high voltage motor solid state soft starter, which is mainly suitable for squirrel cage asynchronous and synchronous motors' starting and stopping control and protection. It adopts high-quality series connection silicon controlled rectifiers to control the output voltage with no gradient, so that the motor is smoothly started and stopped. It has overload, phase loss, starting peak overcurrent and other fault protection functions. Using it can effectively avoid the harmful impact of motor starting current on the power grid, and can use large-power motors under limited power grid capacity and extend their service life.


Tenghui TGRJ Series Medium and High Voltage Motor Solid State Soft Starter User Manual - cover page
Brand
腾辉
Category
motor starter
Document type
User Manual
Language
Chinese
Pages
21
File format
PDF
File size
1 MB
Published
03 November, 2023
Updated
03 November, 2023
MD5 checksum
85401375A9D584CE6308864F414BF874

About this manual

Chinese user manual for the Tenghui TGRJ series medium and high voltage motor solid state soft starter, used for starting and stopping squirrel-cage asynchronous and synchronous motors at 6 kV and 10 kV in a power range of 200 kW to 15000 kW. It covers the model designation, operating conditions, technical performance data, the thyristor working principle and the main features of the device.

The manual then explains the control modes and stopping methods (current limit, voltage exponential and linear curves, current exponential and linear curves, kick-start torque, free stop, soft stop and braking), the parameter settings such as start mode, start voltage/current, start time and current limit, terminal descriptions, installation and commissioning, and a fault code table with causes and remedies. Safety warnings on high-voltage operation, compensation capacitors and insulation testing with a megohmmeter are given at the front. This manual is written in Chinese.

What's inside

  • Product Overview, Model Designation and Operating Conditions
  • Technical Performance and Specifications
  • Working Principle
  • Device Features
  • Operating Instructions and Starting Modes
  • Terminal Description
  • Installation and Commissioning
  • Common Fault Handling
  • Soft Starter Cabinet Appearance and Internal Structure

Specifications

Power range200 kW to 15000 kW
Rated operating voltage1 kV to 15 kV
SupplyThree-phase AC 6 kV–10 kV (+10%/-15%), 50 Hz
Rated short-circuit withstand capability≥20 kA
Overload capability500% for 30 s, 120% continuous
Current-limit starting current100–500% (adjustable to load)
Ramp voltage starting time0–120 s
Protection degreeIP20 (self-cooled), IP00 (forced-air cooled)
CommunicationStandard RS485 interface
Ambient temperature-25 °C to +45 °C
Cabinet dimensions (H*D*W)2300 mm x 1500 mm x 1000 mm

Frequently asked questions

Which types of motors can the TGRJ soft starter control?

It is mainly used for starting, stopping, controlling and protecting squirrel-cage asynchronous motors and synchronous motors.

Where may power factor compensation capacitors be connected?

Compensation capacitors for improving power factor may only be connected to the input of the soft starter, never to the output, otherwise the thyristors will be damaged.

Can a megohmmeter be used to measure insulation between the input and output of the soft starter?

No. Measuring the insulation resistance between input and output with a megohmmeter may damage the thyristors and the control board through overvoltage.

How many protection functions does the soft starter have?

The soft starter has 11 protection functions; when one operates, it stops immediately and the LCD shows the current fault.

Download PDF (1 MB)