This manual describes the GUB series of distribution boxes, switchgear and control components and their installation, commissioning and maintenance.
The ROSE Systemtechnik GUB series consists of explosion-protected enclosures used as distribution boxes, switchgear and control components. They are approved for hazardous areas zones 1, 2, 21 and 22, but not zones 0 and 20, and can be fitted with standard electrical components with arcing or sparking parts according to customer specifications.
The manual covers safety instructions, standards compliance, function, technical data, installation, commissioning, and inspection or maintenance. Technical data include IECEx and ATEX certification, IP66 protection, a 1.1 kV AC/DC rated operating voltage, marine-grade copper-free aluminum construction, ambient-temperature ranges, and cable-entry limits. Installation instructions cover upright mounting with four screws, opening and closing the cover, O-ring or lubricant sealing, and the use of certified cable glands and accessories. This manual is written in Chinese.
| Enclosure material | Marine-grade copper-free aluminum alloy |
|---|---|
| Surface finish | RAL 7035 |
| Protection rating | IP66 according to IEC 60529:2013 & EN 60529:1992+A2:2013 |
| Rated operating voltage | 1.1 kV AC/DC nominal |
| Gas explosion protection | Ex db IIC T6/T5/T4 Gb |
| Dust explosion protection | Ex tb IIIC T85 °C/T100 °C/ T135 °C Db |
| IECEx certificate number | IECEx DEK 18.0076X |
| EC type examination certificate number | DEKRA 18ATEX0120X |
| Grounding | 2 external, 1 internal |
| Mounting | 4 mounting holes |
They can be used in zones 1, 2, 21 and 22, but not in zones 0 and 20.
The enclosures have protection rating IP66 according to IEC 60529 and EN 60529.
The rated operating voltage is 1.1 kV AC/DC; the stated rating is nominal and higher ratings can be agreed with the manufacturer.
Before closing, apply Anabond 662 or an equivalent such as Fuchs Unitemp 2 to the flange surfaces of the cover and body, then tighten the cover bolts.