IPC 200 frequency and voltage control device is a device used for frequency and voltage stability control. It has functions such as low frequency judgment, low voltage judgment, over frequency judgment and over voltage judgment. It is mainly used for low frequency and low voltage load shedding, and can also be used for low frequency de-listing and low voltage de-listing. The device simultaneously measures two-section bus voltage, configures 8 low-frequency wheels and 8 low-voltage wheels, and can directly cut off 24 load lines. The low-frequency reduction and low-voltage reduction can customize each output, and can select different lines.
The Aipukeshi IPC 200 is a frequency and voltage control device for power system stability control. It provides low-frequency, low-voltage, over-frequency, and over-voltage judgment, and the basic version is mainly used for low-frequency and low-voltage load shedding and can also be used for low-frequency and low-voltage splitting. It measures two bus voltages, has eight low-frequency rounds and eight low-voltage rounds, and can directly trip 24 load circuits.
The manual covers the device's technical parameters, operating principles, hardware composition, settings and configuration, software structure and panel operation, reliability, commissioning, and operation and maintenance precautions. It lists mechanical and environmental data such as a 4U enclosure of 482 mm × 177 mm × 340 mm, a normal operating temperature of -5 to 40 °C, a rated AC voltage of 100 V or 57.7 V, and a rated frequency of 50 Hz. This manual is written in Chinese.
| Enclosure dimensions | 482 mm × 177 mm × 340 mm; embedded mounting |
|---|---|
| Normal operating temperature | -5 to 40 °C |
| Limit operating temperature | -10 to 55 °C |
| Storage and transport temperature | -25 to 70 °C |
| Relative humidity | 5% to 95% |
| Atmospheric pressure | 70 kPa to 106 kPa |
| Rated AC voltage | 100 V or 57.7 V |
| Rated frequency | 50 Hz |
| Voltage measurement error | ≤±0.5% (0.2–1.2 UN, 49–51 Hz) |
| Frequency measurement error | ≤±0.01 Hz (45–55 Hz) |
| df/dt measurement error | Less than 0.1 Hz/s |
| du/dt measurement error | Less than 0.05 UN/s |
It is used for frequency and voltage stability control and provides low-frequency, low-voltage, over-frequency, and over-voltage judgment functions.
It can directly trip 24 load circuits; low-frequency and low-voltage load shedding each have eight rounds.
It uses DL/T667-1999, based on the IEC60870-5-103 standard.
The rated frequency is 50 Hz.