This manual introduces the features and usage methods of the lightweight single-phase rail-mounted electric energy meter
This Chinese user manual describes the Yongnuo Electric lightweight single-phase DIN-rail energy meter. The meter has an LCD display, RS485 communication with two protocols and an active-energy pulse output; the manual states that its performance meets GB/T17215, GB/T17883 and DL/T614 requirements.
The manual gives technical parameters such as 1.0 accuracy class, 220 V rated voltage, 10(40) A current specification and 1600 imp/kWh pulse constant, then explains installation on a 35 mm DIN rail, the wiring diagram, the energy pulse output, the items shown on the display pages and the communication address/read-write data formats. This manual is written in Chinese.
| Accuracy class | 1.0 |
|---|---|
| Rated voltage | 220 V |
| Current specification | 10 (40) A |
| Operating frequency | 50 Hz or 60 Hz |
| Pulse constant | 1600 imp/kWh |
| Pulse output | Optocoupler-isolated open collector, pulse width 80 ms ± 20 ms |
| Communication | RS485 supporting Modbus-RTU and DL/T645-2007 |
| Normal operating temperature | -10 °C to +45 °C |
| Limit operating temperature | -20 °C to +55 °C |
| Storage temperature | -40 °C to +70 °C |
| Relative humidity | ≤95 % (no condensation) |
| Mean time between failures | ≥50000 h |
| Dimensions (L × W × H) | 88.7 × 18.5 × 61.5 mm |
| Mounting | 35 mm standard DIN rail |
The RS485 communication supports both the Modbus-RTU protocol and the DL/T645-2007 specification.
The pulse constant is 1600 imp/kWh, meaning 1600 pulses are output for every 1 kWh accumulated.
It should be mounted indoors in a ventilated, dry place using the 35 mm standard DIN rail method, with wiring done according to the diagram on the side of the meter.
By default the 1P DIN-rail meter shows energy, voltage, current, active power, power factor, frequency, communication address, baud rate, data format and pulse constant.