Marathon Electric PM500 Hybrid Analog/Digital Voltage Regulator Installation Manual

PM500 Hybrid Analog/Digital Voltage Regulator Installation Manual


Marathon Electric PM500 Hybrid Analog/Digital Voltage Regulator Installation Manual - cover page
Brand
Marathon Electric
Category
Other Electronics
Document type
Installation Guide
Language
English
Pages
8
File format
PDF
File size
371 KB
Published
03 November, 2023
Updated
03 November, 2023
MD5 checksum
8FFE0CB75C11E2020B9788ACD1E6A640

About this manual

The PM500 is a hybrid analog/digital voltage regulator from Marathon Electric, a Regal brand, for generator applications. This installation manual covers its specifications, DIP switch settings, adjustments, wiring connections, and installation.

The document also includes safety warnings and cautions, resale information, an outline drawing, and a note that it is not intended to provide operational instructions.

What's inside

  • Specifications
  • Dip Switch Setting
  • Adjustment
  • Wiring Connections
  • Installation
  • Outline Drawing
  • Warnings & Cautions
  • Resale of Goods
  • Important Information

Specifications

Sensing input voltage220-600 VAC, 50/60 Hz
Selectable sensing voltage ranges175-280 VAC at 220 VAC; 330-515 VAC at 380/440 VAC; 420-660 VAC at 480/600 VAC
Sensing phase selectionSingle or 3 phase
Power input voltage30-260 VAC, 40-500 Hz, single phase
Output voltage85 VDC at 110 VAC input; 170 VDC at 220 VAC input
Output currentContinuous 5 A max.; intermittent 7 A for 10 sec
Fuse5 x 20 mm S505-5A (slow blow type)
Voltage regulation< ±0.5% (with 4% engine governing)
Voltage build-upResidual voltage at AVR terminal >5 VAC at 25 Hz
Thermal drift0.05% per °C change in AVR ambient
External volts adjustment5% with 500 ohm 1 watt trimmer; 10% with 1000 ohm 1 watt trimmer
Excitation resistance>9 ohm
Max. power dissipation12 watt
Current compensation1 or 5 A, >0.2 VA; max. ±7% at power factor ±0.7
Analogue voltage input0-15% at 0-10 VDC or 0 to ±5 VDC
Under frequency protection50 Hz system knee point at 47 Hz; 60 Hz system knee point at 57 Hz
Response time<1 cycle
Plastic mounting torque30-50 Kgf.cm
Dimensions150 mm L x 135 mm W x 55.5 mm H
Weight470 g ±2%
OVP level voltage220 V: 310-330 VAC; 380 V: 560-580 VAC; 480 V: 700-720 VAC

Frequently asked questions

What is the sensing voltage range of the PM500?

The sensing input accepts 220 to 600 VAC at 50 or 60 Hz.

What is the continuous output current?

Continuous output current is 5 A maximum, with 7 A intermittent for 10 seconds.

What are the under-frequency protection knee points?

The factory setting uses 47 Hz for 50 Hz systems and 57 Hz for 60 Hz systems.

What mounting torque is specified for the plastic mounting?

Plastic mounting torque is 30 to 50 Kgf.cm.

Download PDF (371 KB)