This file is the product manual of a certain power adapter, which introduces the use, installation and storage of the product
This instruction manual is for the Loxone 200035 Series power supply. It gives safety warnings and explains the input and output terminals, the V.ADJ voltage adjust trimmer, the DC OK optocoupler, and the input and output voltage ranges.
The document also covers OVP and OCP, peak output current, output ripple and noise, series operation, isolation and withstand voltage tests, DIN-rail mounting, output derating, wiring and EMC, external fuse rating, UL508 conditions, and checks to make before concluding the unit is at fault.
| Input voltage range | Single phase 85 to 264 VAC (47 to 63 Hz) |
|---|---|
| Output | 24 VDC, 10 A |
| Peak output current | 120% for 10 seconds |
| Operating ambient temperature | Maximum 70 °C |
| Storage temperature | -40 to +85 °C |
| Relative humidity | 5 to 95% (No Dewdrop) |
| Withstand voltage | 4243 VDC between input and output for 1 minute |
| Isolation resistance | More than 100 MOhm at 500 VDC |
| External fuse rating | 250 VAC / 6.3 A |
| EMC emissions | EN55011/EN55032 Class B, EN61204-3 Class A |
It accepts single-phase 85 to 264 VAC at 47 to 63 Hz.
Disconnect the input voltage from the power supply for a minute, then re-apply it.
It is closed when the output voltage is greater than 80% of nominal output voltage.
Tilt the unit slightly rearwards and fit it over the top hat rail, then slide it downward until it hits the stop.