This instruction manual explains how to use the Surge Counter effectively and safely
This instruction manual for the OTOWA SCA-20N surge counter explains safe installation and use. It covers fixing the base to a DIN rail or with M4 screws, installing the CT, and connecting the main body.
The manual describes counting when lightning current above 100 A flows through the CT, a maximum operating current of 50 kA, and count reset by applying DC9V. It also includes notices for indoor use and careful handling.
| Maximum operating current | 50 kA (8/20 μs or 10/350 μs) |
|---|---|
| Counting threshold | More than 100 A |
| Operating interval | About 1 second |
| Count rollover | Counts from zero again after more than 99 counts |
| Terminal screw and recommended tightening torque | M3.5; 0.8 to 1.3 N·m |
| Mounting | DIN rail or M4 screws |
| Use location | Indoor only |
The maximum operating current is 50 kA for 8/20 μs or 10/350 μs waveforms.
The counter increments when lightning current of more than 100 A flows through the CT.
Apply DC9V again to the terminals on the base; the count on the indicator returns to zero.
No. The manual states that the product should be used indoor only.