JD Auspice SPD T8 Portable Surge Protective Device Tester User Manual

SPD T8 User Manual, introduce the usage of the product


JD Auspice SPD T8 Portable Surge Protective Device Tester User Manual - cover page
Brand
JD Auspice
Category
Test Set
Document type
User Manual
Language
English
Pages
13
File format
PDF
File size
919 KB
Published
03 November, 2023
Updated
03 November, 2023
MD5 checksum
CFB7325A4BB459DFDC0A9EB3E33C1867

About this manual

The SPD T8 is a portable tester from JD Auspice Co., Ltd. designed for on-site testing of surge protective devices. It measures both the nominal voltage and the leakage current of different SPDs so users can judge the status of the components. It handles voltage limiting type components (MOV, TVS, Zener diode) and voltage switching type components (gas discharge tube, solid discharge tube, spark gap).

The manual covers safety precautions, the items included in the tester box, standards and applications, general and technical specifications, control functions, the operation procedure for voltage and leakage current measurement, battery replacement, maintenance and repair, troubleshooting, and technical enquiry contact details. The tester is powered by four 1.5V LR6 alkaline batteries and can produce a testing voltage of up to 1000V.

What's inside

  • Safety Precaution
  • Packaging
  • Introduction
  • Standards, applications
  • Specification
  • Control Function
  • Operation Procedure
  • Procedure for Batteries Replacement
  • Maintenance and Repair
  • Troubleshooting

Specifications

Dimensions (Length x Width x Deep)252 mm x 121 mm x 50 mm
Power supply4 x 1.5V LR6 alkaline batteries
Maximum output voltage≤ 1500V (no load)
Maximum overload current2 mA
Case protection levelIP65
Leakage current measurementRange 0~199.9 μA, resolution 0.1 μA, accuracy 5% + 10
1mA DC reference voltage ranges50V~600V and 500V~1000V, resolution 1V, accuracy 3% + 5
Operation humidity≤ 75%
Calibration cycleOnce a year (recommendation)

Frequently asked questions

What does the SPD T8 tester measure?

It measures the nominal voltage and the leakage current of surge protective devices, so users can determine the status of the components from the readings.

What batteries does the SPD T8 tester use?

It uses four 1.5V LR6 alkaline batteries as its power supply.

What should I do when the LCD shows LOBAT?

LOBAT means the battery supply is low, so the batteries have to be replaced, otherwise measurement accuracy will be affected.

What is the maximum output voltage of the tester?

The maximum output voltage is ≤ 1500V with no load.

How do I test an unknown SPD?

Set the operation mode selector to UN, set the test-voltage range selector to 600V, connect the component with the two tester rods and press TEST for 2 seconds until a reading in V and a beep appear; if the reading exceeds 600V, repeat the test with the 1000V range.

Download PDF (919 KB)