This manual introduces the installation steps of the Smart Connect Multi-loop Fire Alarm System.
The Smart Connect Multi-loop is a modular intelligent fire alarm control panel with a 4.3 inch colour touchscreen, designed for life safety and property protection. The manual describes panel types (SMART6, SMART6/32, SMART10/64, SMART10/P/64, SMART26/64, SMART26/P/64 and the SMART/REP repeater), enclosure dimensions, mounting, mains and battery wiring, initial power-up, and the access levels available to the public, responsible person, installer/engineer and authorised service engineer.
The second part covers field wiring for the SCM-LCM loop card module, SCM-ACM alarm circuit module, SCM-MIM input module, SCM-RM relay output, SCM-ZMM zone monitor module and SCM-NM network module, together with their specifications, the 400W power supply, panel printer maintenance, fault finding, standby battery requirements, loop device address setting and product codes.
| Loop card module (SCM-LCM) loop voltage | 35V nominal |
|---|---|
| Maximum loop current | 450mA |
| Maximum loop capacity | 250 addresses |
| Maximum loop length | 2KM |
| Maximum loop resistance | 22Ω (+ to +), 22Ω (- to -) |
| SCM-ACM circuit voltage | 29VDC nominal |
| SCM-ACM maximum circuit current | 500mA per circuit |
| SCM-RM relay switching capacity | 5 A, 30 VDC (resistive); 5 A, 250 VAC (general use) |
| Display | 4.3" colour touch screen |
| Addressable device capacity | Up to 3000 addressable devices |
| Programmable zones | 254 |
| Network size | Up to 64 panel peer-to-peer network |
| Power supply | 400W |
Up to 4, 6 or 12 loop modules, depending on the panel model, with a maximum of twelve loop cards overall.
The module is compatible with MKII-AOP, MKII-AOH, MKII-AHR, MKII-AHF, MKII-AHF/CS90, ZAI-MI, ZAIO-MI, ZAZM-MI, ZAIO/230, ZASC-MI, MKII-SSB, MKII-AXT, MKII-AXTB, ZRAP and ZRAPB devices.
The default user access code is 0001, and the default engineer password is 9999.