ASCO NUMATICS SentronicD Digital Electronic Pressure Regulator 608/609 Display Keypad Installation Manual

This document is about SentronicD Digital Electronic Pressure Regulator Series 608/609 with Display and Keypad installation manual


ASCO NUMATICS SentronicD Digital Electronic Pressure Regulator 608/609 Display Keypad Installation Manual - cover page
Brand
ASCO Numatics
Category
Industrial Supply
Document type
Installation Guide
Language
English
Pages
39
File format
PDF
File size
9 MB
Published
02 November, 2023
Updated
02 November, 2023
MD5 checksum
01729BDEFA1D8CD603280644CFDC478E

About this manual

ASCO NUMATICS SentronicD Series 608/609 is a digital electronic pressure regulator with display and keypad. This installation manual covers description, catalogue numbering, operating elements, manual pressure regulation, operating modes, electrical and pneumatic connections, factory settings, field-programmable settings, technical characteristics, accessories, maintenance, and dimensions and weights.

The manual includes electrical connection diagrams and pin assignments for the 5-pin M12 connector, analog setpoint and outlet pressure relationships, pressure range limits, and factory PID control parameters. It also describes shut-off, overtemperature, undervoltage/overvoltage, and autosafe operating modes.

What's inside

  • Description
  • Catalogue number
  • Operating elements
  • Operating modes
  • Electrical connection
  • Analog setpoint - outlet pressure
  • Pneumatic connection
  • Factory settings for a standard valve
  • Technical characteristics
  • Dimensions and weights

Specifications

Nominal diameter / flow rate (DN 4)DN 4 mm, 470 l/min (SRA)
Nominal diameter / flow rate (DN 8)DN 8 mm, 1300 l/min (SRA)
Maximum outlet pressure3, 6 or 10 bar
Maximum inlet pressure6, 9 or 13 bar
Supply voltage24 V DC, +15%/-10% tolerance, max. 10% ripple
Digital outputPNP, max. 200 mA / 4.8 W
Analog setpoint input0-10 V, 0-20 mA or 4-20 mA
Analog feedback output0-10 V, 0-20 mA or 4-20 mA
Pneumatic connectionsG 1/8, G 1/4, G 3/8, NPT 1/8, NPT 1/4 or NPT 3/8
Cable5-wire 2 m; 6-wire 5 m or 10 m
Connector5-pin M12 female
Overtemperature threshold100 °C
Undervoltage / overvoltagebelow 20 V / above 30 V
Shut-off thresholdbelow 0.5% setpoint
Autosafe current limit1000 mA (DN 8) or 560 mA (DN 4) for more than 20 s
Factory setpoint0 bar at 0 V / 0 mA / 4 mA
Factory span3, 6 or 10 bar at 10 V / 20 mA
ControllerPID; proportional gain 4.0; integration 0.1 s; derivation 8 ms

Frequently asked questions

How is manual pressure regulation activated?

Press both arrow buttons beneath the display during power-up; the display shows H n d and the yellow LED stays on.

What happens when the setpoint is below 0.5%?

The coil current is switched off and the valve is fully exhausted.

What supply voltage does the valve require?

24 V DC with a tolerance of +15%/-10% and a maximum ripple of 10%.

What does the red LED indicate?

It is off in normal operation, on for low voltage, and flashing for overvoltage.

Download PDF (9 MB)