This manual introduces the requirements of the 17th Edition of the Wiring Regulations, and how to use Hager's junction boxes and connection boxes to meet these requirements.
This Hager guide explains requirements of the 17th Edition Wiring Regulations (BS 7671:2008) for electrical connections, with a focus on junction boxes used in lighting and power final circuits. It also refers to Building Regulations Part P in England and Wales and the Scottish Building Standards Agency Technical Handbook.
The guide describes downlighter junction box connections, cable clamping, maintenance-free terminals and accessibility requirements. A product selection guide and selection chart list Hager junction box references J501, J803, J804, J201, J301, J401 and J601 with terminal ratings.
| Downlighter junction box terminal rating | 16 A (J501) |
|---|---|
| Maintenance-free junction box terminal ratings | 32 A (J803), 20 A (J804) |
| Traditional junction box terminal ratings | 20 A (J201), 20 A (J301), 30 A (J401), 20 A (J601) |
| Maintenance-free terminal conductor range | 0.5 mm² to 4.0 mm²; up to four conductors |
The selection guide says traditional junction boxes are acceptable where the location is accessible and there is a suitable fixing position.
They must be accessible for inspection, testing and maintenance. Where boarding, carpet or similar covering is laid over them, maintenance-free terminals should be used.
The guide states that maintenance-free terminals allow up to four conductors from 0.5 mm² to 4.0 mm².
It has cable clamps that secure the sheath of solid and flexible conductors as they enter the enclosure, so there is no undue mechanical strain on the terminations.