This manual contains detailed wiring instructions for Worcester Greenstar gas boilers
This Worcester wiring guide covers Greenstar gas-fired boilers, including Greenstar Ri Regular, Greenstar CDi Regular, Greenstar CDi System, Greenstar CDi Combi, Greenstar FS CDi Regular, Greenstar HF CDi Combi, Greenstar Si Combi, Greenstar i Junior Combi and Greenstar i System. It provides wiring diagrams for configurations such as S-Plan, Y-Plan, 2 port valves, mid position valve, radiator heating zones and underfloor heating.
The introduction covers new complete system installations and existing installations and zone requirements under Part L1a. Wiring diagrams show connections for time controllers, thermostats, zone valves, pumps and a 230V mains fused spur, using L for Live, N for Neutral and E for Earth, and include frost protection for the Greenstar i System.
| Mains voltage | 230V |
|---|---|
| Frost protection pump on | below 8°C |
| Frost protection pump off | above 9°C |
| Frost protection heating demand | below 5°C until above 12 °C |
| Pump overrun | 3 minute |
The wiring diagrams show 230V mains voltage.
New complete heating system installations must conform to current building regulations Part L1a.
When the primary temperature drops below 8°C the pump is switched on.
For boiler replacements on an existing system, it is not necessary to zone the upstairs and downstairs differently.