LABC Warranty Technical Manual Section 17 Electrical Services

This document introduces the construction requirements and specifications for building electrical services


LABC Warranty Technical Manual Section 17 Electrical Services - cover page
Brand
LABC Warranty
Category
Other
Document type
Other
Language
English
Pages
8
File format
PDF
File size
911 KB
Published
02 November, 2023
Updated
02 November, 2023
MD5 checksum
B43FB7F3C2CFABD8FC4CB154ABBEF465

About this manual

Section 17 (Electrical Services) of the LABC Warranty Technical Manual sets out functional requirements for electrical work in dwellings. It covers workmanship, design and general provisions for installation, including conformity with Building Regulations and BS 7671, and the positioning and protection of cables and fittings within shaded zones.

The section then details socket and outlet requirements per room, heights for sockets, switches and consumer units, supplementary earth bonding in bathrooms with plastic or metal pipework, and cabling within walls and floors. It ends with guidance on notching and drilling, chasing masonry cavity walls, services in framed walls and fire stopping around penetrations.

What's inside

  • Workmanship
  • Materials
  • Design
  • Mains: Positioning and protection of cables and fittings
  • General provisions for installation
  • Supplementary earth bonding
  • Mains: Socket and outlet requirements
  • Positioning of sockets and switches
  • Mains: Cabling and services within walls and floors
  • Fire stopping

Specifications

Socket outlet height above floorAt least 450 mm
Consumer unit height above floor1350 mm to 1450 mm
Cooking appliance supplyMinimum 30 A
Horizontal shaded zone below ceiling150 mm
Horizontal chase depth (masonry)One-sixth the thickness of the single leaf
Vertical chase depth (masonry)One-third the thickness of the leaf
Metal plate protection in framed wallsServices within 25 mm of the face of stud
13A outlets required in kitchen/utility8 (at least 4 per room if separate)
13A outlets required in living/family room8

Frequently asked questions

How high above floor level should socket outlets be located?

Socket outlets should be located at least 450 mm above floor level.

Is supplementary bonding required in kitchens or utility rooms?

No. Supplementary bonding is required in rooms containing a bath or shower, and is not required within kitchens, utility rooms or washrooms.

How deep can chases in masonry cavity walls be?

Horizontal chases should not exceed one-sixth of the single leaf thickness and vertical chases one-third of the thickness.

Which standard should electrical installations follow?

All electrical installations should be in accordance with the relevant regional Building Regulations and BS 7671.