This document introduces the construction requirements and specifications for building electrical services
Section 17 (Electrical Services) of the LABC Warranty Technical Manual sets out functional requirements for electrical work in dwellings. It covers workmanship, design and general provisions for installation, including conformity with Building Regulations and BS 7671, and the positioning and protection of cables and fittings within shaded zones.
The section then details socket and outlet requirements per room, heights for sockets, switches and consumer units, supplementary earth bonding in bathrooms with plastic or metal pipework, and cabling within walls and floors. It ends with guidance on notching and drilling, chasing masonry cavity walls, services in framed walls and fire stopping around penetrations.
| Socket outlet height above floor | At least 450 mm |
|---|---|
| Consumer unit height above floor | 1350 mm to 1450 mm |
| Cooking appliance supply | Minimum 30 A |
| Horizontal shaded zone below ceiling | 150 mm |
| Horizontal chase depth (masonry) | One-sixth the thickness of the single leaf |
| Vertical chase depth (masonry) | One-third the thickness of the leaf |
| Metal plate protection in framed walls | Services within 25 mm of the face of stud |
| 13A outlets required in kitchen/utility | 8 (at least 4 per room if separate) |
| 13A outlets required in living/family room | 8 |
Socket outlets should be located at least 450 mm above floor level.
No. Supplementary bonding is required in rooms containing a bath or shower, and is not required within kitchens, utility rooms or washrooms.
Horizontal chases should not exceed one-sixth of the single leaf thickness and vertical chases one-third of the thickness.
All electrical installations should be in accordance with the relevant regional Building Regulations and BS 7671.