This manual provides installation and operation guidelines for the THISION WH hot water heater.
This is the operation and installation manual (document number C3078 / 12103187) for the THISION WH 02/2011 water heater. It sets out the general regulations and applicable norms, describes the construction layout and operating principle of the unit, gives a technical data table, and then covers installation and connection of the water heater, commissioning of the water and hydraulic system, gas supply, flue and air intake connections, preparation for first start-up, combustion analysis, gas tightness checks and shut-down. Further sections deal with lockouts, a maintenance checklist, replacing the electrodes, cleaning the condensate receptacle and syphon, inspection of the combustion chamber, water pressure and quality, safety devices and a maintenance protocol.
The THISION WH is described as a fully modulating water heater whose control unit adapts the modulation ratio to the heat demand by controlling fan speed, and as a standalone DHW charging system consisting of a buffer tank, plate heat exchanger and a boiler, with the option of connecting two units in parallel where there is a high hot water demand. The technical data table gives figures for THISION L 65, THISION L 85 and THISION L 120, including nominal heat output, efficiency, gas consumption, gas pressures, flue gas data, water connections and electrical connection.
| Nominal heat output at 80-60 °C (max/min) | 60.8/10.1 kW (THISION L 65); 81.1/13.4 kW (L 85); 111.6/18.7 kW (L 120) |
|---|---|
| Efficiency at 80/60 °C | 97.4 % (L 65 and L 85); 97.6 % (L 120) |
| Gas pressure H-gas | 20 mbar |
| Maximum gas pressure | 50 mbar |
| Water pressure (max/min) | 6/1 bar |
| Maximum temperature setpoint | 90 °C |
| Max. water temperature (high limit thermostat) | 100 °C |
| Electrical connection | 230 V, 50 Hz, 10 A mains connection fuse |
| IP class | IPX4D |
| Flue gas connection | 100 mm |
| Air intake connection (room sealed use) | 100 mm |
| Condensate connection | 22 mm |
| Built-in water recirculation pump capacity | 600 l/hr at the 20 kPa setting |
The technical data gives a maximum water pressure of 6 bar and a minimum of 1 bar.
The gas pressure for H-gas is 20 mbar, with a maximum gas pressure of 50 mbar.
Yes. Where there is a high demand for hot water there is an option to connect two units together in parallel, with the pipework arranged so that flow is distributed evenly through both units.
A 230 V, 50 Hz supply with a 10 A mains connection fuse.