This document is a CIX6435/30 & CIX6535/30 User's Guide manual
Data-Linc Group prepared this user guide for the proper installation, operation, and maintenance of a Communication Interface Extender (CIX) system. The guide covers the CIX6435 master Ethernet and serial interface for wireless I/O remotes (1 Watt, 900 MHz FHSS), the CIX6430 remote with 8 discrete inputs, 8 discrete outputs, 4 analog inputs, and 4 analog outputs, and the CIX6535 master (500 mW, 2.4 GHz FHSS) with CIX6530 remote. It also covers the CIX/EXR wired I/O remote, which connects via RS-232 or RS-485.
The document includes FCC and RF exposure warnings, requirements, features, applications, installation, setup, master and remote configuration, radio settings, and technical specifications. It states that the transceivers are line-of-sight and that external antennas may be needed if line of sight does not exist or units are mounted into grounded metal enclosures.
| CIX6435/6535 power | 10-28 VDC |
|---|---|
| CIX6430/6530 power | 12-28 VDC |
| CIX6435/6535 Ethernet connections | 1 RJ45 straight-through 10BaseT; 1 RJ45 crossover 10BaseT |
| Maximum transmitted output power, CIX6435/CIX6430 | 955 mW |
| Maximum transmitted output power, CIX6535/CIX6530 | 500 mW |
| Minimum antenna separation | 23 cm |
| Discrete output rating | 200 mA each |
| Analog outputs | 4-20 mA or 0-10 VDC |
| Operating temperature, CIX6430/6530 | -40 °F to 150 °F (-40 °C to 65 °C) |
| CIX remote I/O capacity | 8 discrete inputs, 8 discrete outputs, 4 analog inputs, 4 analog outputs |
The CIX6435/6535 requires 10-28 VDC.
Up to 16 CIX I/O Remote units can communicate to a single CIX Master unit.
Their maximum transmitted output power is 500 mW.
The listed operating temperature is -40 °F to 150 °F (-40 °C to 65 °C).