Georgin UI Configurable Converter Trip Amplifier User Manual

UI Configurable converter - Trip amplifier is a configurable electrical value converter with universal input and trip amplifier function. It can be configured by PC with ProgressX Manager software and a standard USB cable connection, or using the BlueSet backlit removable programming console.


Georgin UI Configurable Converter Trip Amplifier User Manual - cover page
Brand
GEORGIN
Category
Converter
Document type
User Manual
Language
English
Pages
36
File format
PDF
File size
3.7 MB
Published
02 November, 2023
Updated
02 November, 2023
MD5 checksum
ABB80CD7DD1499635064BCCFEE7E883F

About this manual

The Georgin UI is a configurable universal electrical value converter with a trip amplifier function. It has a universal input and is described in the manual as monitoring or regulating physical parameters such as temperature, pressure, position, level, and rate.

The manual covers device characteristics, electrical and structural specifications, intrinsic safety parameters, installation, operation, configuration with ProgressX Manager or the BlueSet console, diagnostics, and maintenance. Depending on version, the UI provides relay outputs and a proportional 4-20 mA or 0-10 V analog output.

What's inside

  • Function
  • Presentation of the device
  • Electrical characteristics
  • Connection
  • Installation
  • Operation
  • Configuration
  • Diagnostic and maintenance

Specifications

Number of channels1 or 2 depending on model
Power supply21.6 to 300 Vdc; 99 to 253 Vac; 24 to 48 Vdc optional
Consumption≤ 4 VA
Response time<2 seconds
Operating temperature-20 to 60°C
WeightApprox. 200 g
MountingOn rail DIN EN 50022
Analog output (M1 to M3)4-20 mA
Analog output (M4 to M6)0-10 V

Frequently asked questions

How can the UI be configured?

It can be configured by PC with ProgressX Manager software and a standard USB cable, or with the BlueSet backlit removable programming console.

What physical parameters can the UI monitor or regulate?

The UI monitors or regulates temperature, pressure, position, level, rate, and similar physical parameters.

What is the UI power supply range?

The universal power supply accepts 21.6 to 300 Vdc and 99 to 253 Vac; an optional rear connector provides 24 to 48 Vdc.

What relay outputs are available depending on model?

Models M1 and M4 have one SPDT alarm threshold relay; M2 and M5 have two NO alarm relays, and M3 and M6 have two NC alarm relays.

Download PDF (3.7 MB)

More GEORGIN Manuals


View all GEORGIN manuals →