NIVETEC MultiCONT P-200 Installation and Programming Manual

This manual provides installation and programming instructions for NIVETEC's MultiCONT product


NIVETEC MultiCONT P-200 Installation and Programming Manual - cover page
Brand
Nivetec
Category
Other device
Document type
User Manual
Language
Portuguese
Pages
58
File format
PDF
File size
2 MB
Published
01 November, 2023
Updated
01 November, 2023
MD5 checksum
92FF02DF21CB5CE5E873A72B491B549B

About this manual

This manual covers the NIVETEC MultiCONT P-200 controller and visualizer, a HART master that can power two-wire transmitters and perform complex control tasks. It supports up to 15 common NIVELCO transmitters or 4 Ex-certified instruments in 2- or 3/4-wire installations, with RS485 series networking, a large LCD dot matrix panel, relays, and 4...20 mA analog outputs.

The document explains HART communication, electrical connections, MultiCONT programming, remote transmitter programming, error codes, adjustment protection, fuse replacement, and appendices such as manufacturer identification codes and menu systems. This manual is written in Portuguese.

What's inside

  • Introduction
  • Technical data
  • Coding
  • Dimensions
  • Electrical connection
  • MultiCONT programming
  • Errors and error codes
  • Adjustment protection
  • Fuse replacement
  • Appendices

Specifications

Maximum common NIVELCO transmitters15
Maximum Ex-certified instruments4
Transmitter wiring2-wire or 3/4-wire
DisplayLarge LCD dot matrix panel
Series communicationRS485
Analog outputs4...20 mA
Ex-certified version installationNon-hazardous areas only
HART loop resistance250 to 500 Ω
HART data transfer rate1200 bits/sec
HART logic 1 modulation frequency1200 Hz
HART logic 0 modulation frequency2200 Hz
HART multidrop devicesUp to 15 in parallel
Multidrop transmitter currentConstant 4 mA
Ex version external resistor820 Ω between L- and SH
Short TAG length8 characters
Descriptor lengthUp to 16 characters
NIVELCO factory ID151

Frequently asked questions

How many transmitters can the MultiCONT P-200 communicate with?

It supports up to 15 common NIVELCO transmitters, or 4 Ex-certified instruments.

What loop resistance is required for HART communication?

The system must contain a resistance between 250 and 500 Ω.

What is the HART data transfer rate?

The HART data transfer rate is 1200 bits/sec.

How many devices can be connected in a HART multidrop system?

The addressable HART system can accommodate up to 15 devices connected in parallel.

Download PDF (2 MB)