This manual provides basic operating instructions for Jehcu units, including installation, commissioning and maintenance, to ensure safe and correct use.
This manual covers installation and operation of J&E Hall scroll and reciprocating condensing units for medium- and low-temperature applications, including the JEHCCU, JEHS CU and JEHSCU series.
It includes safety and health information, site location, installation clearance, compressor handling, field piping, pressure testing, leak detection, decommissioning, service and maintenance, F-gas regulations, troubleshooting, specifications, outline drawings and electrical data.
| Supported refrigerants, medium-temperature units | R404A, R134a, R407C |
|---|---|
| Supported refrigerant, low-temperature units | R404A |
| Recommended piping length | 25 m or less |
| Maximum height difference, outdoor unit above indoor unit | Less than 25 m |
| Maximum height difference, outdoor unit below indoor unit | Less than 4 m |
| Oil trap interval on suction pipe | Every 4 m height |
| Factory test pressure, high side | 28 barg (405 psig) |
| Factory test pressure, low side | 19 barg (275 psig) |
| Minimum compressor oil level | Not lower than one quarter of the oil sight glass |
Medium-temperature units list R404A, R134a and R407C, while low-temperature units list R404A.
The recommended piping length is 25 m or less.
The factory test pressures are 28 barg (405 psig) on the high side and 19 barg (275 psig) on the low side.
The oil level should not be lower than one quarter of the compressor oil sight glass.