J&E Hall JEHCCU, JEHS CU and JEHSCU Condensing Unit Installation and Operation Manual

This manual provides basic operating instructions for Jehcu units, including installation, commissioning and maintenance, to ensure safe and correct use.


J&E Hall JEHCCU, JEHS CU and JEHSCU Condensing Unit Installation and Operation Manual - cover page
Brand
J&E Hall
Category
Other products
Document type
Installation Guide
Language
English
Pages
216
File format
PDF
File size
52.8 MB
Published
01 November, 2023
Updated
01 November, 2023
MD5 checksum
E50E130F479A1FE0EC5956A15D3DAEE1

About this manual

This manual covers installation and operation of J&E Hall scroll and reciprocating condensing units for medium- and low-temperature applications, including the JEHCCU, JEHS CU and JEHSCU series.

It includes safety and health information, site location, installation clearance, compressor handling, field piping, pressure testing, leak detection, decommissioning, service and maintenance, F-gas regulations, troubleshooting, specifications, outline drawings and electrical data.

What's inside

  • Nomenclature
  • Safety and Health
  • Installation & Commissioning
  • Decommissioning & Disposal
  • Service and Maintenance
  • F gas Regulations
  • Trouble Shooting
  • Specifications
  • Outline Drawings
  • Electrical Data

Specifications

Supported refrigerants, medium-temperature unitsR404A, R134a, R407C
Supported refrigerant, low-temperature unitsR404A
Recommended piping length25 m or less
Maximum height difference, outdoor unit above indoor unitLess than 25 m
Maximum height difference, outdoor unit below indoor unitLess than 4 m
Oil trap interval on suction pipeEvery 4 m height
Factory test pressure, high side28 barg (405 psig)
Factory test pressure, low side19 barg (275 psig)
Minimum compressor oil levelNot lower than one quarter of the oil sight glass

Frequently asked questions

Which refrigerants are listed for these condensing units?

Medium-temperature units list R404A, R134a and R407C, while low-temperature units list R404A.

What is the recommended field piping length?

The recommended piping length is 25 m or less.

What factory pressure test values are given?

The factory test pressures are 28 barg (405 psig) on the high side and 19 barg (275 psig) on the low side.

What compressor oil level is required?

The oil level should not be lower than one quarter of the compressor oil sight glass.