This manual provides operating instructions and safety instructions for the Ex px control unit APEX.
This manual provides detailed instructions for installing, operating, and maintaining the Bartec Ex p Control Unit APEX Set, an explosion-proof purge control system. It includes safety guidelines, electrical and pneumatic connections, commissioning procedures, and troubleshooting. The system consists of an Ex p control unit, Ex e control station, and purge unit, designed for Zone 1 environments and compliant with ATEX/IECEx standards.
The manual is intended for technically qualified personnel and covers configuration, function checks, maintenance intervals, and technical specifications including voltage, temperature range, and relay ratings.
| Operating temperature range | -25 °C to +50 °C @ T4 |
|---|---|
| Mains voltage | AC (variant) 100 Vac to 230 Vac, +/- 10% |
| Maximum power consumption | 35 W (incl. purge valve) |
| Enclosure material | Polyester, Glass Fiber Reinforced |
| IP degree of protection | IP 64 acc. to IEC/EN 60079-0 |
| Dimensions | 250 (W) x 300 (H) x 120 (D) mm |
The operating temperature range is -25 °C to +50 °C @ T4.
The mains voltage requirement is AC (variant) 100 Vac to 230 Vac, +/- 10%.
The IP rating is IP 64 acc. to IEC/EN 60079-0.
The dimensions are 250 (W) x 300 (H) x 120 (D) mm.