NC-920 48 Bit DIO Module is an industrial automation control module that can be connected to a PC via RS-232 serial port. It supports multiple communication protocols and multiple input and output methods, which can meet the needs of different applications.
NETCOM NC-920 is a PC/104 module for embedded applications in industrial environments, providing 48 TTL/DTL/CMOS compatible digital I/O lines. The lines are arranged in two groups, each with three 8-bit ports (Port A, Port B, and Port C) that can be configured as inputs or outputs under 8255 Mode 0.
Port C is split into upper and lower 4-bit sections, and an interrupt on change of state can occur when Port C bit 3 or bit 7 of each group changes state. The manual covers module configuration, installation, register structure, programming, and application examples.
| Input/output lines | 48 |
|---|---|
| Operation mode | 8255 Mode 0 |
| Interrupt trigger | Port C bit 3 or bit 7 change of state |
| Isolation | 2500 V |
| Ports | Two groups; each has Port A, B, and C (8-bit) |
| Interrupt options | Pair jumper-selectable to level 9(2), 5, 10, 11, 12 or 15 |
| Noise margin hysteresis | 0.4 V typ. |
| Input/output level | TTL/DTL compatible; CMOS/dry contact compatible |
| Input low voltage (VIL) | 0.8 V max |
| Input high current (IIH) | 20 uA max at VI = 2.7 V |
| Input low current (IIL) | -0.2 mA max at VIL = 0.4 V |
| Output high voltage (VOH) | 2.4 V min at IOH = -3 mA |
| Output low voltage (VOL) | 0.4 V max at IOL = 12 mA |
| Output high current (IOH) | -15 mA max |
| Output low current (IOL) | 24 mA max |
| I/O connector | 50-pin male mating connector |
| I/O cable type | Ribbon twisted pair cable; ribbon stripline cable |
| Bus interface | PC/104 bus |
| I/O locations occupied | 8 consecutive addresses |
| +5 V current | 0.4 A typ. |
| Dimensions | 95 mm x 90 mm |
| Storage temperature range | -25 to 85 C |
| Relative humidity | To 90%, non-condensing |
| Default base address | 220 Hex (544 Dec) |
The factory default base address is 220 Hex (544 Dec).
It provides 48 TTL/DTL/CMOS compatible digital I/O lines.
Interrupt occurs when Port C bit 3 or bit 7 of each group changes state.
It requires +5 V at 0.4 A typical.