This manual provides step-by-step instructions for installing, operating, and maintaining the Renova EP10000000R electro-pneumatic converter. It includes safety warnings, technical specifications, and maintenance procedures. The device is a precision electronic pressure regulator for pneumatic applications requiring fine pressure control. Installation must be performed by qualified personnel, and protective equipment is required. The manual also covers transport, storage, and disposal guidelines.
| Output pressure | 0 ... 6 bar |
|---|---|
| Operating pressure | At least 1,5 bar above maximum required output pressure |
| Flow | Up to 200 N l/min |
| Air consumption (typical) | ≤ 3 N l/min |
| Ambient temperature | 0 ... +60 °C |
| Response time | < 500 ms from 0 to 100% or < 150 ms from 100 to 0% of output pressure into a 10cc load |
| Degree of protection | IP20 |
| Hysteresis and deadband | < 1% of span |
| Linearity | < 1,5% of span |
| Vibration immunity | < 3% output shift for ± 2 g 15 ... 150 Hz |
| Weight | 0,20 kg |
| Electrical input signal | 2-pin versions or 1 ... 10 V |
| Electrical power input | 24 V d.c. ±10% |
| Loop resistance | 250 Ω max |
The output pressure range is 0 to 6 bar.
The maximum flow rate is up to 200 N l/min.
The ambient temperature range is 0 to +60 °C.
The response time is less than 500 ms from 0 to 100% or less than 150 ms from 100 to 0% of output pressure into a 10cc load.