Microsensor Link Rod Float Level Switch User Manual

This is a manual of a float switch. It introduces the product features, parameters, working principle, installation and use, precautions, etc.


Microsensor Link Rod Float Level Switch User Manual - cover page
Brand
Microsensor
Category
Rod float level switch
Document type
User Manual
Language
Chinese
Pages
2
File format
PDF
File size
231 KB
Published
31 October, 2023
Updated
31 October, 2023
MD5 checksum
BCD10C684C633EA88F927F2B43837FF2

About this manual

This manual provides instructions for the Microsensor link rod float level switch, a liquid level control device using a magnetic reed switch actuated by a float with an internal magnet. It covers daily maintenance, unboxing inspection, key usage precautions, basic parameters, working principle, installation guidelines, contact protection circuits, wiring details, and troubleshooting.

The document specifies operating temperature range of -20°C to 120°C (200°C max), pressure ratings for metal and plastic versions, contact capacities up to 50W/250VAC, and maximum working currents of 1A. It emphasizes proper wiring through a relay or PLC, avoidance of inductive loads without protection, and warns against adjusting the factory-set float position. This manual is written in Chinese.

What's inside

  • Daily Maintenance
  • Unboxing and Inspection
  • Key Usage Precautions
  • Basic Parameters
  • Working Principle
  • Installation Instructions
  • Contact Protection Circuits
  • Wiring and Contact Description
  • Common Faults and Troubleshooting

Specifications

Temperature Range-20°C to 120°C (200°C max)
Pressure RatingMetal: -1.0 to 3.5 MPa; Plastic: 0 to 0.5 MPa
Contact Capacity50W/250VAC or 200VDC; 40W/250VAC; 10W/110VAC
Rated Current0.2A (50W); 0.16A (40W); 0.1A (10W)
Maximum Working Current1A (50W or 40W); 0.5A (10W)

Frequently asked questions

What are the voltage and current limits for the float switch?

The switch voltage must be less than the reed switch maximum voltage (125V AC for 10W, 240V AC/200V DC for 50W) and current less than maximum working current (0.5A for 10W, 1A for 50W/40W).

How should the float switch be wired?

Open the junction box, pass the cable through the cable gland, tighten the gland screw, and connect power and contact wires to the corresponding terminals according to the nameplate and terminal block markings.

What protection circuits are recommended for inductive loads?

For inductive loads such as motors, relays, or solenoid coils, connect a protection circuit in parallel with the load, such as an RC snubber, varistor, or diode.