Su Dian SDKG-151 High-Voltage Switch Mechanical Characteristic Tester User Manual

SDKG-151 type switch characteristic testing instrument is a special instrument for detecting high-voltage circuit breaker mechanical dynamic characteristics. It can simultaneously measure the three-phase different phase, the same phase different phase, the moving contact stroke, the moving contact overtravel, the closing (opening) time, the closing (opening) bounce time, the just closing (opening) speed, the closing (opening) maximum speed and the closing (opening) average speed of three-phase six contacts.


Su Dian SDKG-151 High-Voltage Switch Mechanical Characteristic Tester User Manual - cover page
Brand
Sudian
Category
Industrial Robot
Document type
User Manual
Language
Chinese
Pages
9
File format
PDF
File size
289 KB
Published
31 October, 2023
Updated
31 October, 2023
MD5 checksum
8D16BBB4C351C3B3BC5471ED1C849B71

About this manual

The Su Dian SDKG-151 is a specialized instrument designed to detect the mechanical dynamic characteristics of high-voltage circuit breakers. It integrates a computer, printer, measurement interface circuits, and operating power into a single unit. The device features two displacement sensors suitable for different distances and precisions, automatically identifying the system to measure distance and speed for oil, SF6, and vacuum high-voltage circuit breakers. This manual is written in Chinese.

What's inside

  • Overview
  • Instrument Functions and Features
  • Instrument Structure
  • Technical Indicators
  • Connection of Breaker Lines
  • Installation of Sensors
  • Test Parameter Display
  • Printer Output
  • Troubleshooting Guide

Specifications

Operating Voltage RangeDC 60V~220V
Power SupplyAC 220V ± 10% 50HZ
Simultaneous Break MeasurementOne to six breaks
Measurement Error (Time)± 0.1 ms
Measurement Error (Distance)± 1 mm
Max Line Speed≤ 7.0 m/s
Operating Temperature-10 ℃— +40 ℃

Frequently asked questions

How many breaks can be measured simultaneously?

The instrument can measure one to six breaks simultaneously.

What is the measurement error for time and distance?

The time measurement error is ± 0.1 ms, and the distance measurement error is ± 1 mm.