ZXKC-VI circuit breaker characteristic testing instrument is a high voltage switch mechanical characteristic testing instrument, which can accurately measure the mechanical dynamic characteristic parameters of various voltage levels of less oil, multi-oil, vacuum, and six-fluorine sulfur circuit breakers.
The ZXKC-VI is a circuit breaker characteristic testing instrument, also called a high-voltage switch mechanical characteristic tester in the manual. The text states that it was designed with reference to GB1984-2003 and DL/T846.3-2004 for measuring mechanical dynamic characteristic parameters of low-oil, bulk-oil, vacuum and sulfur hexafluoride high-voltage circuit breakers, including time, speed, travel and current.
The manual covers the front panel, break signal wiring, open/close control, sensor installation and menu settings. It also documents 12 break signal channels, a time measurement range of 0.01 ms to 10000 ms, storage for 100 measurement data sets, a high-speed thermal printer, common on-site problems, terminology, troubleshooting and daily maintenance. This manual is written in Chinese.
| Break signal channels | 12 channels |
|---|---|
| Time measurement range | 0.01 ms to 10000 ms |
| Time measurement accuracy | 0.1% ±2 digits from 1 ms to 100 ms; 0.5% ±2 digits above 100 ms |
| Speed measurement range | 1 mm sensor: 0.01–25.00 m/s; 0.1 mm sensor: 0.001–2.50 m/s; 360° sensor: 0.01–25.00 m/s |
| 50 mm linear displacement sensor | Resolution 0.1 mm, travel 0.1–50 mm |
| Data storage | 100 measurement data sets |
| Printer | High-speed thermal printer |
| Power supply | AC/DC 220 V ±10%; 50 Hz ±2% |
| DC output voltage | 25–265 V continuously adjustable |
| DC output current | ≤20 A (short time) |
| Dimensions | 360 × 250 × 140 mm |
| Operating temperature | -10 °C to +50 °C |
| Relative humidity | ≤90% |
It measures mechanical dynamic characteristic parameters of low-oil, bulk-oil, vacuum and sulfur hexafluoride high-voltage circuit breakers.
The stated range is 0.01 ms to 10000 ms.
It can store 100 measurement data sets.
The manual says connecting ground first completes the discharge circuit, so induced voltage on the break signal wires can be discharged to ground.