MG5000 High Voltage Digital Insulation Resistance Tester is the latest generation of high voltage digital insulation resistance tester launched by Sanwa Meter. This meter adopts a large screen backlight LCD display, with a measurement pen and alligator clips, a wide measurement range, high accuracy, and simple operation, and is an ideal measurement tool for the power, electronics, petrochemical, metallurgy and other industries.
This is the Chinese-language product manual for the Sanwa Meter MG5000 high voltage digital insulation resistance tester. It covers safety precautions and warning symbols, the maximum overload protection ratings of each terminal, intended use and features, the names of the parts and what the LCD shows, the TL-5K test leads and optional accessories, and the function descriptions.
The measurement section explains how to check the instrument before use, how to measure AC/DC voltage and insulation resistance, the discharge function, DAR (dielectric absorption ratio) and PI (polarization index) measurement, the voltage characteristic and how to use the GUARD terminal. It closes with maintenance, calibration and inspection, cleaning, battery and fuse replacement, after-sales service, and the general and measurement specifications. This manual is written in Chinese.
| Maximum input voltage at LINE (L) to ground (E) terminals | DC/AC 1000 V; maximum overload protection DC/AC 1100 V |
|---|---|
| Maximum voltage at GUARD (G) terminal | No voltage input allowed; overload protection DC/AC 30 V |
| AC voltage measurement range | 30-1000 V, ±(3 %rdg+2 dgt) |
| DC voltage measurement range | 30-1000 V, ±(3 %rdg+2 dgt) |
| AC voltage accuracy frequency range | 50 / 60 Hz |
| Insulation resistance test voltage outputs | 5 ranges |
| Safety standard and overvoltage categories | IEC 61010-1 CAT.IV 600 V / CAT.III 1000 V |
| Battery indicator levels | 3 segments 10.6 V or above; 2 segments 8.6-10.5 V; 1 segment 7.6-8.5 V; low battery 6.9-7.5 V (accuracy not guaranteed); 6.8 V or below |
| Auto power off | Display turns off and the meter enters power-saving mode after about 10 minutes |
| Backlight auto off | About 60 seconds |
| Test lead length | 3 m for the LINE red, earth black and guard green leads (TL-5K) |
| Optional long LINE lead | TL-5K-15 pluggable line lead (red), 15 m |
| Policy terminal polarity during insulation test | EARTH terminal is positive, LINE terminal is negative |
Press and hold the TEST switch for at least 2 seconds to start measuring; press it for at least 1 second to stop.
DAR is the resistance after 60 seconds of applied voltage divided by the resistance after 30 seconds or 15 seconds.
PI is the resistance after 10 minutes of applied voltage divided by the resistance after 1 minute.
The factory setting is 15 seconds; with the power off, hold DISPLAY and turn the function switch on, then use DISPLAY to switch between 00:30 and 00:15.