Terminator ZT is for use as an adjustable control/limiter thermostat with Thermon heating cables systems
This document provides installation procedures for the Terminator ZT thermostat, which serves as an adjustable control or limiter for Thermon TESH series constant watt heating cables. It covers safety warnings, required tools, and component approvals for hazardous and ordinary locations.
| Ambient Temperature Range (T5) | -60°C ≤ Ta ≤ +50°C |
|---|---|
| Ambient Temperature Range (T6) | -60°C ≤ Ta ≤ +40°C |
| Maximum Current (T5) | 25 Amps Max |
| Protection Rating | IP66 |
| Terminal Torque | 1.4 Nm (12.4 lb-in) |
It is used as an adjustable control/limiter thermostat for TESH Series Constant Watt Heating Cables.
The Terminator-LN-Tool is required for installation.
The minimum bending radius is 6 times the cable outer diameter.
Yes, a ground-fault protection device is required due to the risk of electrical shock, arcing and fire.