This manual introduces the basic technical parameters, usage environment, installation sequence, control panel, operating instructions, maintenance and maintenance of the flow meter.
The ACH3150 air volume hood uses a pitot-tube principle to automatically measure airflow at multiple points and calculate average airflow in m3/h or ft3/min. It is used to measure airflow through supply air outlets and diffusers and can also measure return air outlets; the backlit display makes readings easy to see in dark locations.
The instrument stores up to 128 groups of data with up to 32 measurements per group, and stored data can be viewed, printed, or uploaded to a computer. It is powered by four AA batteries and is intended for use within the stated temperature, humidity, and gas restrictions. This manual is written in Chinese.
| Measurement range | 150-3000 m3/h |
|---|---|
| Measurement accuracy | ±3%FS |
| Resolution | 1 m3/h |
| Hood size (standard) | 610 x 610 mm (24 x 24 in) |
| Weight | 4.5 kg (with 610 x 610 mm hood) |
| Power supply | 4 AA batteries |
| Power | 12 hours |
| Operating temperature | -10°C to +60°C |
| Relative humidity | 30% to 70% RH |
| Data storage | 128 groups, up to 32 measurements each |
It can store 128 groups of data, and each group can store up to 32 measurement results.
Place the hood where no air can pass through it, then press [校正/上] to calibrate.
Open the menu, select unit conversion, choose the desired unit, then press [菜单/确认].
Corrosive gases, gases containing metal particles, and gases with large particles or high-concentration dust.