Manta Electric (Shanghai) Co., Ltd. MLC filter compensation kit user manual, mainly introduces MLC filter compensation kit model, composition, installation wiring diagram, installation technical requirements, MATPR filter inductor, MATPC filter compensation capacitor external appearance and technical parameters.
This manual is for the Manta Electric MLC filter compensation kit. It presents model information by voltage level, resonant frequency and rated capacity in kvar, and lists the components as MATPR series filter reactors and MATPC series filter capacitors, referring to the related manuals for the reactor and capacitor descriptions.
For installation, it specifies fans at the bottom and top of the cabinet, the capacitor above the bottom fan, the reactor above the capacitor, and the thyristor on the cabinet front at the side of the capacitor, with 50-100 mm spacing between capacitor and reactor and more than 30 mm between capacitor and thyristor. Each fan must be at least 65 W at 50 Hz and starts at 35 °C under thermostat control, capacitor spacing is at least 20 mm and the stated ambient temperature range is -25 °C to +45 °C, and the reactor temperature switch must be connected in series in the control circuit. It also lists technical parameters for the MATPR reactor and MATPC capacitor and requires checks for loose connection conductors before operation. This manual is written in Chinese.
| Reactor system voltage | 230V, 400V, 690V, 1000V |
|---|---|
| Reactor rated frequency | 50Hz |
| Reactor core linear current | 1.7In |
| Reactor insulation heat-resistance grade | H |
| Capacitor overcurrent | 2.0In |
| Capacitor inrush current | 200In |
| Capacitor service life | 130000 hours |
| Capacitor protection rating | IP20 |
| Fan power | At least 65W at 50Hz each |
The kit consists of MATPR series filter reactors and MATPC series filter capacitors.
The distance between the capacitor and reactor should be 50-100mm.
The fan thermostat starts at 35℃.
The listed system voltages are 230V, 400V, 690V and 1000V.