Manta Electric MLC Filter Compensation Kit User Manual

Manta Electric (Shanghai) Co., Ltd. MLC filter compensation kit user manual, mainly introduces MLC filter compensation kit model, composition, installation wiring diagram, installation technical requirements, MATPR filter inductor, MATPC filter compensation capacitor external appearance and technical parameters.


Manta Electric MLC Filter Compensation Kit User Manual - cover page
Brand
Manta Electric
Category
Other Electronics
Document type
User Manual
Language
Chinese
Pages
4
File format
PDF
File size
267 KB
Published
31 October, 2023
Updated
31 October, 2023
MD5 checksum
7D24405EDA42EA7F317F73639D3EF7CB

About this manual

This manual is for the Manta Electric MLC filter compensation kit. It presents model information by voltage level, resonant frequency and rated capacity in kvar, and lists the components as MATPR series filter reactors and MATPC series filter capacitors, referring to the related manuals for the reactor and capacitor descriptions.

For installation, it specifies fans at the bottom and top of the cabinet, the capacitor above the bottom fan, the reactor above the capacitor, and the thyristor on the cabinet front at the side of the capacitor, with 50-100 mm spacing between capacitor and reactor and more than 30 mm between capacitor and thyristor. Each fan must be at least 65 W at 50 Hz and starts at 35 °C under thermostat control, capacitor spacing is at least 20 mm and the stated ambient temperature range is -25 °C to +45 °C, and the reactor temperature switch must be connected in series in the control circuit. It also lists technical parameters for the MATPR reactor and MATPC capacitor and requires checks for loose connection conductors before operation. This manual is written in Chinese.

What's inside

  • Model description
  • Components
  • Installation wiring diagram
  • Installation technical requirements
  • Outline description
  • Technical parameters

Specifications

Reactor system voltage230V, 400V, 690V, 1000V
Reactor rated frequency50Hz
Reactor core linear current1.7In
Reactor insulation heat-resistance gradeH
Capacitor overcurrent2.0In
Capacitor inrush current200In
Capacitor service life130000 hours
Capacitor protection ratingIP20
Fan powerAt least 65W at 50Hz each

Frequently asked questions

What are the components of the MLC filter compensation kit?

The kit consists of MATPR series filter reactors and MATPC series filter capacitors.

What distance should be kept between the capacitor and reactor?

The distance between the capacitor and reactor should be 50-100mm.

At what temperature does the fan thermostat start?

The fan thermostat starts at 35℃.

What system voltages are listed for the MATPR reactor?

The listed system voltages are 230V, 400V, 690V and 1000V.

Download PDF (267 KB)