OC-F08 fixed gas detector operating manual. This manual introduces the use of the detector, precautions, maintenance and other contents
The Oceanus OC-F08 is a fixed gas detector built with an original imported sensor: catalytic combustion for combustible gas, electrochemical for oxygen and toxic gas, NDIR infrared for carbon dioxide and methane, and PID for VOCs. It has a dashboard display interface with three-color backlight that shows data, fault and alarm states, and it offers optional 4~20mA, RS485, 0~5V, 0~10V, 200~1000Hz or relay outputs for connection to a DCS, PLC or the company's control system.
This operating manual covers the safety notices, installation position and mounting, internal terminal connections and wiring, the normal working mode and self-test sequence, the setting interface, sensor care and maintenance, warranty and the technical specification table with the detecting gas list. The detector is wall or pipe mounted in a cast aluminum body with IP66 protection and Ex d IIC T6 explosion-proof index.
| Applicable Gas | Oxygen, Combustible gas, toxic gas, etc |
|---|---|
| Detecting Range | According to the detected gas |
| Accuracy | ≤±3%F.S |
| Repeatability | ≤±1% |
| Response Time (T90) | ≤20s |
| Working Voltage | 24V DC (16~30VDC) |
| Output Signals (Standard) | Three-wire system 4~20mA, for PLC, DCS, etc. |
| Operating Environment | Temperature -30℃~60℃; humidity ≤95%RH (non-condensing); pressure 86kPa~106kPa |
| Installation Means | Wall mounted, Pipe type (Thread: M40*1.5) |
| Material of Body | Cast aluminum |
| Explosion-proof Index | Ex d IIC T6 |
| Protection Grade | IP66 |
| Transmit Distance | ≤2000m |
| Dimension | 210 mm×140 mm×92 mm (L×W×H) |
| Weight | About 1.5Kg |
| Standards | GB15322.1-2003, GB3836.1-2010, GB3836.2-2010, GB3836.4-2010 |
The manual says the fixed gas detector should be calibrated every 6 months, and for some sensors every 3 months is suggested.
It carries a 12-month warranty from the day it leaves the factory, covering quality problems of breakdown under normal usage.
The flow rate should be controlled between 160 and 250 ml/min, otherwise the measurement will not be stable.
The manual recommends 3 years for the catalytic combustion sensor, 2 years for the electrochemical sensor and 3~5 years for the PID sensor.