Gems Sensors Warrick Series 26NM Control Installation and Operation Bulletin

This bulletin is an instruction manual for WARRIOR® Series 26NM Control.


Gems Sensors Warrick Series 26NM Control Installation and Operation Bulletin - cover page
Brand
Gems Sensors
Category
Other
Document type
Installation Guide
Language
English
Pages
2
File format
PDF
File size
123 KB
Published
31 October, 2023
Updated
31 October, 2023
MD5 checksum
0ADBFA33057DAF2D0FE89D6D670BE60A

About this manual

This two-page bulletin provides installation and operation information for the Gems Sensors Warrick Series 26NM Control. It covers socket mounting, wiring per the wiring diagram, and installation of the control module in the socket.

The bulletin describes automatic reset, manual reset, the optional power outage feature, the test feature, and the LED status indicator. It also lists specifications including contact ratings, supply voltage, power consumption, sensitivity, time delays, and UL listings.

What's inside

  • Installation
  • Specifications
  • Sensitivity vs. Maximum Probe Wire Distance
  • Operation
  • Automatic Reset
  • Manual Reset
  • Manual Reset Optional Power Outage Feature
  • Test Feature
  • LED Status Indicator
  • Wiring Diagram

Specifications

Control DesignSolid-state components in a clear Lexan plug-in style housing; not NEMA rated.
Contact Design1 SPDT (1 form A), N.O. non-powered contacts.
Contact LifeMechanical: 5 million operations; electrical: 100,000 operations minimum at rated load.
Supply VoltageFactory configured: 24V, 120V, 220V, or 240V AC (+10%/-15%), 50/60 Hz.
Power ConsumptionApproximately 4.4 VA with relay energized at 24/120/220/240 VAC.
Secondary Circuit2.3 VAC RMS voltage on probes; less than 1 milliampere source capability.
SensitivityFactory programmed to 4.7K, 10K, 26K, 50K, or 100K Ohms.
Time DelaysStandard LLCO: 0.5 sec. on rising level and 3 sec. on falling level; optional 0-90 sec. delays in 1-sec. increments.
ListingsUL Limit Control Listing (UL-353) for 24VAC and 120VAC line-powered units only.

Frequently asked questions

What supply voltages are available for the Series 26NM Control?

Factory-configured supply voltages are 24V, 120V, 220V, or 240V AC at 50/60 Hz.

How can the LLCO circuit be tested without dropping the boiler water level?

Hold the reset button down for 3 seconds to trip the LLCO circuit and simulate a dry probe; press reset again to return to normal.

What does it mean if the LED is blinking?

A fault has been detected; the blink pattern indicates the fault type, and the bulletin advises contacting the factory for assistance.

What is the standard time delay on falling level?

The standard LLCO time delay is 3 seconds on falling level.