This bulletin is an instruction manual for WARRIOR® Series 26NM Control.
This two-page bulletin provides installation and operation information for the Gems Sensors Warrick Series 26NM Control. It covers socket mounting, wiring per the wiring diagram, and installation of the control module in the socket.
The bulletin describes automatic reset, manual reset, the optional power outage feature, the test feature, and the LED status indicator. It also lists specifications including contact ratings, supply voltage, power consumption, sensitivity, time delays, and UL listings.
| Control Design | Solid-state components in a clear Lexan plug-in style housing; not NEMA rated. |
|---|---|
| Contact Design | 1 SPDT (1 form A), N.O. non-powered contacts. |
| Contact Life | Mechanical: 5 million operations; electrical: 100,000 operations minimum at rated load. |
| Supply Voltage | Factory configured: 24V, 120V, 220V, or 240V AC (+10%/-15%), 50/60 Hz. |
| Power Consumption | Approximately 4.4 VA with relay energized at 24/120/220/240 VAC. |
| Secondary Circuit | 2.3 VAC RMS voltage on probes; less than 1 milliampere source capability. |
| Sensitivity | Factory programmed to 4.7K, 10K, 26K, 50K, or 100K Ohms. |
| Time Delays | Standard LLCO: 0.5 sec. on rising level and 3 sec. on falling level; optional 0-90 sec. delays in 1-sec. increments. |
| Listings | UL Limit Control Listing (UL-353) for 24VAC and 120VAC line-powered units only. |
Factory-configured supply voltages are 24V, 120V, 220V, or 240V AC at 50/60 Hz.
Hold the reset button down for 3 seconds to trip the LLCO circuit and simulate a dry probe; press reset again to return to normal.
A fault has been detected; the blink pattern indicates the fault type, and the bulletin advises contacting the factory for assistance.
The standard LLCO time delay is 3 seconds on falling level.