Erie Water Treatment Oxydizer Water Filter - Fe, Mn, H2S Technical Manual

This file is an instruction manual for a water purifier, which mainly introduces the use, installation and maintenance methods of the water purifier.


Erie Water Treatment Oxydizer Water Filter - Fe, Mn, H2S Technical Manual - cover page
Brand
Erie water treatment
Category
Other products
Document type
Service Manual
Language
English
Pages
24
File format
PDF
File size
2.2 MB
Published
31 October, 2023
Updated
31 October, 2023
MD5 checksum
7453E3AB05EB03F4F99C18A3BC8547D7

About this manual

This technical manual is for the Erie Water Treatment Oxydizer water filter for iron, manganese and hydrogen sulfide. It states that the filter removes specific undesired substances and will not purify polluted water or make it safe to drink.

The manual covers warnings and safety, operating conditions and requirements, installation, start-up, the electronic control panel, maintenance, hydraulic flow diagrams, troubleshooting, electrical wiring, default parameter settings, exploded views and technical data.

What's inside

  • Warning & Safety instructions
  • Operating conditions & Requirements
  • Installation
  • Start-up
  • Electronic control panel
  • Maintenance
  • Hydraulic flow diagrams
  • Troubleshooting
  • Electrical wiring diagram
  • Technical data

Specifications

pH for iron removal6,8 - 9,0
pH for manganese removal8,0 - 9,0
pH for iron and manganese removal8,0 - 8,5
Maximum iron (Fe2+)15 mg/L
Maximum manganese (Mn2+)2 mg/L
Maximum hydrogen sulfide (H2S)5 mg/L
Maximum organic matter4,0 mg/L
Maximum chlorine1,0 mg/L
Operating pressuremin. 1,4 / max. 8,3 bar
Optimal operating pressure3 bar (±½ bar)
Operating temperaturemin. 4 / max. 38 °C
Electrical connection230V-50Hz
Operating voltage24VAC
Transformer230/24V-50Hz
Drain hose diameter13 mm
Air gap pipe size32 mm pipe
Minimum piping to water heater3 m

Frequently asked questions

Does this water filter purify polluted water?

No. It removes specific undesired substances and will not purify polluted water or make it safe to drink.

What is the recommended operating pressure?

The system is configured to perform optimally at 3 bar (±½ bar), with an operating pressure range of 1.4 to 8.3 bar.

Should the start-up regeneration be performed immediately?

No. It is strongly recommended to postpone the start-up regeneration by 24 hours.

What electrical supply does the filter use?

The filter works on 24VAC and is equipped with a 230/24V-50Hz transformer; the electrical connection is 230V-50Hz.

Download PDF (2.2 MB)