This document provides troubleshooting guidelines to help users solve problems with their water heater.
This Unit Heater troubleshooting guide lists common complaints, LED codes, and possible causes or solutions. It covers checks for control board voltage, transformer output, exhaust blower operation, pressure switch tubing, gas valve supply, flame sensor current, and spark igniter gap.
The text also gives replacement steps for boards, motors, switches, transformers, and fuses, and refers to installation manuals or rating plates for manifold and gas pressure settings.
| Control board ACC terminal voltage | 120 V |
|---|---|
| Transformer secondary voltage | 24 V |
| Flame sensor signal | At least .6 micro amps |
| Spark igniter gap | 1/8 in |
| Control board fuse | 3 A |
There should be 120 volts at the ACC terminal on the control board; if not, the board is bad.
The flame signal should be at least .6 micro amps.
The spark igniter gap should be 1/8".
Check for 120 volts at the CMB terminal on the control board; if present, replace the motor, and if not, replace the board.