Chiltrix V18 In-Line Heater Installation and Operation Manual

V18 Installation and Operation Manual


Chiltrix V18 In-Line Heater Installation and Operation Manual - cover page
Brand
Chiltrix
Category
Heater
Document type
User Manual
Language
English
Pages
23
File format
PDF
File size
1.2 MB
Published
31 October, 2023
Updated
31 October, 2023
MD5 checksum
20425E242AA99BE514B84A30D649BAFF

About this manual

The V18 is an in-line heater for Chiltrix air-to-water heat pump systems that adds backup heat in the amount needed through MODBUS communication. It is rated at 5.5 kW at 240 V and can adjust power in increments as small as 27.5 W.

The manual covers indoor vertical installation before loads, 208-240 V 30 A GFCI power wiring, control and Modbus wiring, chilled-water sealing, heater element replacement, manual reset, and bulletins for power failures and outdoor reset.

What's inside

  • Installation
  • Wiring
  • Power Wiring
  • Control Wiring
  • Modbus Cable
  • Chilled Water Note
  • Heater Element Replacement
  • Manual Reset
  • Power Failure Bulletin
  • Outdoor Reset Bulletin

Specifications

Heating capacity rating5.5 kW (18,760 BTU) at 240 V
Power adjustment increment27.5 W
Standard heating element240 V, 5500 W, 18,760 BTU
Voltage derating at 208 VUp to 4131 W (14,094 BTU)
Required circuit208-240 V, 30 A, GFCI breaker
Pipe fittingsNPT 2 inch female
Thermal reset temperatureBelow 130 F
Controller capacityUp to 3 V18 units

Frequently asked questions

Is the V18 used for domestic hot water backup?

No; the V18 is for space heating backup only.

How must the V18 be mounted?

It must be mounted vertically; horizontal mounting could trap air bubbles.

What electrical circuit is required?

Use a 208-240V 30A circuit with a GFCI breaker.

What sealing is required for chilled-water systems?

Seal around the white ABS cover and inside the Liquidtight conduit with silicone.