Juyu Intelligent JB-TT(TG)-JF999-D fire alarm control unit and fire alarm control unit instruction manual, introduces the composition structure, technical characteristics, main functions, operating interface, alarm display instructions and other contents of the controller.
This is the V1.0 user manual (dated August 2020) for the Jiuyuan Zhineng JB-TT(TG)-JF999-D fire alarm control unit and fire linkage control unit. It describes how the controller is put together, what it does and how it is operated, and it opens with a note that the manual should be read before installing and using the product.
The manual covers the controller's composition and structure, its technical characteristics, its main functions such as fire alarm, fault alarm, fire priority, automatic printing and part shielding, the operating panel and its indicator lamps, alarm display states, and controller operation through the main menu (query, test, settings, installation, system and exit). A power wiring safety warning and contact information close the document. This manual is written in Chinese.
| Wiring | Two-bus, non-polarized |
|---|---|
| Capacity per loop | 200 points per loop at full load (detection and linkage control parts mixed), 15 floor displays |
| Polling cycle | 3 seconds |
| Maximum line distance | 1500 m with multi-strand copper flexible wire of cross-section ≥1.0 mm² |
| Ambient temperature | -10 °C to +50 °C |
| Ambient humidity | ≤95% |
| External power | AC220V, 50Hz |
| Backup power | DC24V 12Ah |
| Maximum controller capacity | 8 bus loops (1600 points), 4 direct linkage units (32 points), one 50-point bus panel and one 90-point bus panel |
| Console cabinet dimensions | 1062 mm (L) × 900 mm (W) × 1350 mm (H) |
| Vertical cabinet dimensions | 480 mm (L) × 550 mm (W) × 1770 mm (H) |
| Interface | Standard RS232 interface for connection to a CRT or for downloading |
The controller's inspection (polling) cycle is 3 seconds.
The long line distance is 1500 m, using multi-strand copper flexible wire with a cross-section of at least 1.0 mm².
It uses a DC24V 12Ah backup battery pack, which is float-charged while main power is present.
The controller automatically switches to battery supply, and the backup power running lamp lights.
Press the silence key first to stop the alarm sound, then press the reset key to return the controller to normal monitoring.