Jiuyuan Zhineng JB-TT(TG)-JF999-D Fire Alarm and Fire Linkage Control Unit User Manual

Juyu Intelligent JB-TT(TG)-JF999-D fire alarm control unit and fire alarm control unit instruction manual, introduces the composition structure, technical characteristics, main functions, operating interface, alarm display instructions and other contents of the controller.


Jiuyuan Zhineng JB-TT(TG)-JF999-D Fire Alarm and Fire Linkage Control Unit User Manual - cover page
Brand
久远智能
Category
Other
Document type
User Manual
Language
Chinese
Pages
10
File format
PDF
File size
692 KB
Published
31 October, 2023
Updated
31 October, 2023
MD5 checksum
592F5DE9F23AF3190969D824A4D8CD0A

About this manual

This is the V1.0 user manual (dated August 2020) for the Jiuyuan Zhineng JB-TT(TG)-JF999-D fire alarm control unit and fire linkage control unit. It describes how the controller is put together, what it does and how it is operated, and it opens with a note that the manual should be read before installing and using the product.

The manual covers the controller's composition and structure, its technical characteristics, its main functions such as fire alarm, fault alarm, fire priority, automatic printing and part shielding, the operating panel and its indicator lamps, alarm display states, and controller operation through the main menu (query, test, settings, installation, system and exit). A power wiring safety warning and contact information close the document. This manual is written in Chinese.

What's inside

  • 控制器特性
  • 控制器主要功能
  • 控制器操作界面
  • 报警显示说明
  • 控制器操作
  • 控制器菜单
  • 电源接线安全警示
  • 联系我们

Specifications

WiringTwo-bus, non-polarized
Capacity per loop200 points per loop at full load (detection and linkage control parts mixed), 15 floor displays
Polling cycle3 seconds
Maximum line distance1500 m with multi-strand copper flexible wire of cross-section ≥1.0 mm²
Ambient temperature-10 °C to +50 °C
Ambient humidity≤95%
External powerAC220V, 50Hz
Backup powerDC24V 12Ah
Maximum controller capacity8 bus loops (1600 points), 4 direct linkage units (32 points), one 50-point bus panel and one 90-point bus panel
Console cabinet dimensions1062 mm (L) × 900 mm (W) × 1350 mm (H)
Vertical cabinet dimensions480 mm (L) × 550 mm (W) × 1770 mm (H)
InterfaceStandard RS232 interface for connection to a CRT or for downloading

Frequently asked questions

What is the polling cycle of the JB-TT(TG)-JF999-D controller?

The controller's inspection (polling) cycle is 3 seconds.

How long can the bus wiring be?

The long line distance is 1500 m, using multi-strand copper flexible wire with a cross-section of at least 1.0 mm².

What backup power does the controller use?

It uses a DC24V 12Ah backup battery pack, which is float-charged while main power is present.

What happens when the main power is cut off?

The controller automatically switches to battery supply, and the backup power running lamp lights.

How is a fire alarm cleared?

Press the silence key first to stop the alarm sound, then press the reset key to return the controller to normal monitoring.