Shandong Kexin Electric CSNB-80 Surge Protector Manual

CSNB-80 series surge protector is designed according to GB18802.1, IEC61643-1 surge protection standard, applicable to AC 50Hz, 220v/380v and below TN-S, TN-C-S, TT, IT power supply systems. Each module has a rated discharge current of In (8/20μs) up to 40kA and a maximum discharge current of Imax (8/20μs) up to 80kA. It has passed the national professional lightning protection II class test and is suitable for areas with high lightning risk (LPZ2 or LPZ2 and LPZ3 intersection areas). It can be applied to the secondary lightning protection of AC power systems. Through the cooperation of the front and rear-stage surge protectors, the lightning energy is gradually released to protect the distribution power supply and terminal power equipment.


Shandong Kexin Electric CSNB-80 Surge Protector Manual - cover page
Brand
Shandong Kexin Electric
Category
Other Electronics
Document type
User Manual
Language
Chinese
Pages
5
File format
PDF
File size
1.6 MB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
1A72846DB5257406CCC6A1139CDCAF6B

About this manual

Shandong Kexin Electric CSNB-80 series surge protector is designed according to GB18802.1 and IEC61643-1 for AC 50 Hz systems up to 220 V/380 V. Each module provides nominal discharge current up to 40 kA and maximum discharge current up to 80 kA (8/20 μs), with protection level not exceeding 1.5 kV.

The manual covers product features and parameters, installation instructions with wiring diagrams, surge protector schematic, product dimensions, and warranty. It describes plug-in modular construction, 35 mm DIN rail mounting, operating conditions, and replacement of failed modules. This manual is written in Chinese.

What's inside

  • CSNB-80 series surge protector
  • Product features and parameters
  • Installation instructions
  • Surge protector schematic
  • Product dimensions
  • Warranty

Specifications

SPD modelCSNB-80/AC385-4P
Rated voltage220 V/380 V
Maximum continuous operating voltage385 V/50 Hz
Nominal discharge current40 kA (8/20 μs)
Maximum discharge current80 kA (8/20 μs)
Protection level≤1.5 kV
Response time≤25 ns
Leakage current≤15 μA
Protection modeL/N-PE; L-N N-PE optional
Design standardGB18802.1
Conductor cross-section16 mm²
Ground conductor cross-section25 mm²
Poles1P, 2P, 3P, 4P optional
Housing materialFlame-retardant plastic
Dimensions108 x 90 x 62 mm
Operating temperature-40 °C to +80 °C
Storage temperature-40 °C to +80 °C
Relative humidity5% to 95% (no condensation)
Protection ratingIP20
AltitudeNot exceeding 3000 m
Warranty3 years

Frequently asked questions

What is the nominal discharge current of the CSNB-80?

Each module has a nominal discharge current In of up to 40 kA (8/20 μs).

Which protection modes are available?

The available protection modes are L/N-PE and L-N N-PE.

What should be done if the module failure indicator turns red?

The surge protector has failed and should be replaced promptly.

What is the warranty period?

The product warranty period is 3 years.