SP-3128 is a 12bit DAC 8-channel analog output + 4-channel digital input module. Channel 0 to 3 can be programmed to output 0-20mA, 4-20mA current analog signals, and channels 4 to 7 can be programmed to output ±10V, 0-10V voltage analog signals. The module is widely used in industrial measurement and control, intelligent instruments and meters, and process control applications. It has high cost performance; RS-485 communication and analog output channels and modules provide 1500V electrical isolation, which can effectively avoid surge interference and other high-voltage shock damage.
The SP-3128 is a 12-bit DAC module providing 8 analog output channels (4 current, 4 voltage) and 4 digital input channels. It communicates via isolated two-wire RS-485 using standard Modbus RTU protocol at baud rates from 4800 to 115200 bps, with 1500 VDC isolation between communication, analog outputs, and the module. Each channel can be independently programmed for output range, startup value, and signal slew rate. The module operates on 12–40 VDC, consumes up to 3 W at 24 VDC, and works in temperatures from –25 °C to 70 °C.
Configuration is performed with the KM Tools software (downloadable from www.kmrxxt.com) after placing the module into setup mode by shorting the Init* and GND terminals. The guide details wiring, register mapping, analog output encoding formulas, step-by-step configuration of serial parameters, analog outputs, and digital inputs, as well as calibration procedures for current and voltage channels. Factory default Modbus address is 1, baud rate 9600, 8 data bits, no parity, 1 stop bit. This manual is written in Chinese.
| Communication Interface | Isolated two-wire RS-485, 1200 m max distance, Modbus RTU, 4800–115200 bps, 8 data bits, configurable stop bit and parity |
|---|---|
| Channels | 12-bit resolution, 8 analog outputs + 4 digital inputs |
| Analog Output Types | Channels 0–3: 4–20 mA, 0–20 mA; Channels 4–7: ±10 V, 0–10 V |
| Isolation Voltage | 1500 VDC |
| Safety Functions | Fail-Safe, system watchdog 1.6 s, communication watchdog 0.1–6553.5 s, DI trigger |
| Current Output Load Capacity | <650 Ω |
| Output Slew Rate | Voltage: 0.0625–64 V/s; Current: 0.125–128 mA/s |
| Accuracy | Better than 0.1% |
| Power Supply | 12–40 VDC, 3 W max at 24 VDC |
| Operating Temperature | –25 °C to 70 °C |
| Storage Temperature | –25 °C to 85 °C |
| Humidity | <95% non-condensing |
| Dimensions | 75 mm × 115 mm × 35 mm |
| I/O Connector | 13-pin pluggable terminal block |
The SP-3128 uses standard Modbus RTU over isolated two-wire RS-485.
It has 8 analog output channels: channels 0–3 support 4–20 mA and 0–20 mA; channels 4–7 support ±10 V and 0–10 V.
Default Modbus address is 1, baud rate 9600, 8 data bits, no parity, 1 stop bit.