This manual provides detailed information on the YT-400 / 405 / 430 / 435 series lock-up valves, including product description, installation instructions, and maintenance instructions.
The Rotork YTC YT-400/405/430/435 series lock-up valves are designed to detect plant pneumatic pressure and block the flow path when signal pressure drops below a set point. This safety feature prevents the flow of pneumatic pressure to the actuator and positioner in case of power failure or pipe breakage, thereby maintaining the current valve opening. The valves are available in single or double acting configurations with aluminum or stainless steel bodies.
| Max. Supply Pressure | 1 MPa (10 bar) |
|---|---|
| Signal Pressure Setting Range | 0.14 ~ 0.7 MPa (1.4 ~ 7 bar) |
| Differential Pressure | Below 0.01MPa (0.1 bar) |
| Housing Material | Aluminum Diecasting or Stainless Steel 316 |
| Weight (Single Acting, YT-400) | 0.47 Kg (1.1 lb) |
The factory default setting pressure level is 0.3 MPa.
The valve blocks the flow path inside the lock-up valve to completely block the flow of pneumatic pressure.
The upper diaphragm may be damaged or foreign material may be attached; replace the assembly or clean the debris.