IDI2015C Single-phase Electrical Parameter Comprehensive Meter is the successor product of IDI Electronic Company's electrical parameter comprehensive meter. This series of products are based on 16-bit single-chip technology, and use large-scale integrated circuits internally to reduce the volume and significantly reduce the failure points. It is precise, meticulous in workmanship, safe, convenient and simple to use, and is in a leading position in the same industry.
The IDI IDI2015C single-phase electrical parameter comprehensive meter is an upgraded electrical parameter measuring instrument from IDI Electronics. It uses 16-bit microcontroller technology and large-scale integrated circuits, and is intended for appliance, lighting, motor, and transformer manufacturers as well as laboratories and quality supervision departments.
The manual covers safety rules, installation, product overview and technical specifications, panel description, operating instructions, maintenance, calibration, and input/output wiring requirements. This manual is written in Chinese.
| Power supply | AC 220V ±10%, 50/60Hz |
|---|---|
| Power consumption | Less than 5 W |
| Dimensions | 105 (H) × 285 (W) × 235 (D) |
| Weight | ≤ 2.5 kg |
| Voltage range | 500 V (display 2.50 V to 499.9 V) |
| Current range | 20 A (display 10.0 mA to 20.00 A) |
| Power range | Up to Umax × Imax W (20 A range) |
| Power factor range | 0 to 1 (display 0.100 to 1.000) |
| Frequency range | 40 Hz to 400 Hz |
| Basic accuracy | 0.5 class |
| Voltage accuracy | ±(0.4% of reading + 0.1% of range) |
| Current accuracy | ±(0.4% of reading + 0.1% of range) |
| Power accuracy (COSφ≥0.5) | ±(0.4% of reading + 0.1% of range) |
| Power accuracy (COSφ<0.5) | ±(0.8% of reading + 0.2% of range) |
| Power factor accuracy | ±0.02 |
| Frequency accuracy | ±0.1 Hz (40 to 400 Hz) |
| Serial interface | RS232/RS485 (optional) |
| Functions | Current and power upper/lower limit alarm, latch, mute |
It uses an AC 220V ±10%, 50/60Hz single-phase power supply.
The total voltage range is 500 V, displayed from 2.50 V to 499.9 V.
It should be carefully inspected and calibrated at least once a year, and more often under production or harsh conditions.
Do not open the case yourself; contact IDI Electronics or an authorized dealer.