YT YT-3400 / YT-3450 Smart Valve Positioner Product Leaflet

The YT-3400/YT-3450 smart positioner has global certified explosion-proof / flameproof housing, auto calibration, LCD display, PST, analog feedback signals, mechanical/transistor switch options, auto/manual switch, PID control, HART communication, front panel push button configuration and other features


YT YT-3400 / YT-3450 Smart Valve Positioner Product Leaflet - cover page
Brand
YT
Category
Electro-Pneumatic Positioner
Document type
Product Leaflet
Language
English
Pages
2
File format
PDF
File size
314 KB
Published
30 October, 2023
Updated
30 October, 2023
Model
YT-3400
MD5 checksum
AF449326E3F6637891EB584A45157B69

About this manual

This leaflet presents the YT-3400 and YT-3450 smart valve positioners. The YT-3400 uses an aluminium die-cast enclosure and the YT-3450 a stainless steel 316 enclosure. Design features listed include an explosionproof/flameproof housing certified for Zone 1 and Division 1 installations, auto calibration with a simple menu structure, an alphanumeric LCD display, a fully adjustable Partial Stroke Test, analogue 4 to 20 mA feedback with mechanical and transistor switch options, an auto/manual switch, PID control and HART communication.

The second page gives dimensions, a specification table and the product code key. Specifications cover input signal, supply pressure, stroke for linear and rotary types, impedance, air, gauge and conduit connections, operating temperature types, linearity, hysteresis, sensitivity, repeatability, air consumption, flow capacity, output characteristics, housing material, ingress protection, explosion protection types, communication and weight. Options include HART protocol communication and 4 to 20 mA feedback and/or limit switch outputs.

What's inside

  • Design features
  • Explosionproof / flameproof housing
  • Auto calibration
  • LCD display
  • Partial Stroke Test (PST)
  • Feedback signal
  • Auto / manual switch
  • PID control
  • HART communication
  • Dimensions

Specifications

Input Signal4 to 20 mA DC
Supply Pressure0.14 to 0.7 MPa / 1.4 to 7 bar / 20 to 102 psi
Stroke (Linear Type)10 to 150 mm (0.4 to 6")
Stroke (Rotary Type)55 to 110°
ImpedanceMax. 450 Ω @ 20 mA DC
Operating Temperature (Standard Type)-30 to +85 °C (-22 to +185 °F)
Linearity±0.5% F.S.
Repeatability±0.3% F.S.
Air ConsumptionBelow 2 LPM (sup = 0.14 MPa) / Below 0.08 CFM (sup = 20 psi)
Flow Capacity70 LPM (sup = 0.14 MPa) / 2.47 CFM (sup = 20 psi)
Ingress ProtectionNEMA 4-4X, IP66
Communication (Option)HART (ver.7)
Weight3.4 kg (7.5 lb) for YT-3400; 7.0 kg (15.4 lb) for YT-3450
MaterialAluminium diecasting (YT-3400); Stainless steel 316 (YT-3450)

Frequently asked questions

What is the difference between the YT-3400 and the YT-3450?

The YT-3400 has an aluminium die-cast housing and the YT-3450 has a stainless steel 316 housing.

What input signal does the positioner use?

The input signal is 4 to 20 mA DC, with a maximum impedance of 450 Ω at 20 mA DC.

What supply pressure range is specified?

The supply pressure range is 0.14 to 0.7 MPa, equivalent to 1.4 to 7 bar or 20 to 102 psi.

What communication protocol is available as an option?

HART (version 7) communication is available as an option, sending commands, position feedback and diagnostics digitally over the current loop.